4.2.3 Enable / Disable channels
This option allows the Millennium II Transmitter channels to be enabled or disabled. The default value is channel
1(CH1) enabled for single sensor models while channel 2(CH2) is permanently disabled. Both channels are enabled for
two sensor models.
1. Enter the main menu by selecting/activating any key to get the “enter main menu” prompt, then activate switch 1
to select “yes”.
2. Select the down arrow key (switch 2) with the magnet, and scroll to “Enable/Disable Channel?
3. Activate the enter key (switch 3) to enter the option. The sub menu options: CH 1 Enabled and CH 2 Enabled
will be highlighted.
4. To disable a channel 1, Activate the enter key (switch 3). “CH1 disabled” will now be highlighted / displayed.
5. To disable channel 2, highlight CH2 Enabled use switch 2, then activate the enter key (switch 3) to configure to
CH2 disabled.
6. To exit the main menu, select “Exit” with enter key at each menu stage (sub menu and main menu).
4.2.4 Viewing and setting alarm levels (points)
This option enables the channel low and high alarm levels to be viewed and set-up. Alarm levels (points) for each
channel are user determined. Alarm Point 1 and Point 2 for channel 1 does not relate to Alarm Point 1 and Point 2 for
channel 2.
1. Enter the main menu by selecting/activating any key to get the “enter main menu” prompt, then activate switch 1
to select “yes”.
2. Activate the up key (switch 1) or the down key (switch 2) until “Set Alarm Level? is highlighted / displayed.
3. Activate switch 3 to enter the Set Alarm Level option. Sub menu options Set CH1 Level’, Set CH2 Level and
‘Exit’ will be displayed. Set CH1 Level being highlighted.
4. To view channel 1 alarm points, activate switch 3. CH1 Point 1 and CH1 Point 2 will be displayed.
5. To view channel 2 alarm points use switch 2, at step 3, highlight Set CH2 Level, then activate switch 3. CH2
Point 1 and CH2 Point 2 will be displayed.
6. To configure channel 1 alarm levels (Point 1 or Point 2), after step 4, use switch 3 to select CH 1 Point 1
(already highlighted) then proceed to step 8, or highlight CH1 Point 2 using switch 2 , then activate switch 3 and
proceed to step 8.
7. To configure channel 2 alarm levels (Point 1 or Point 2), after step 5, use switch 3 to select CH2 Point 1 then
proceed to step 8, or use switch 2 to highlight CH2 Point 2, then activate switch 3 to make a selection. Proceed to
step 8.
8. Use switch 1 to increase the existing values representing previously set alarm levels/points and switch 2 to
highlight and scroll across values.
9. After setting desired alarm points, select “Exit” at each menu stage (sub menu and main menu).