LOCATION OF VENT TERMINATION
When locating vent termination, it is important to observe the minimum clearances shown in Figure 10. You will avoid extra framing by positioning
your fireplace against an already existing framing member. The sides of the fireplace may be positioned directly against combustible walls.
*Check with local codes or with the current CAN/CGA B149 [.1 or .2] Installation Codes for Canada or the USA Installations follow the
current National Fuel Gas Code, ANS Z223.1, also known as NFPA 54.
Fixed
Closed
Openable
Fixed
Closed
Openable
V
V
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
N
H
I
A
N
E
L
D
B
M
A
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPPLY INLET
GAS METER RESTRICTED AREA
(TERMINATION PROHIBITED)
A = clearance above grade, veranda, porch, deck, or balcony
[*12 inches (305mm) minimum]
B = clearance to window or door that may be opened
[12 inches (305mm) minimum]
C = clearance to permanently closed window [minimum 12 inches
(305mm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (610mm) from the
center-line of the terminal [18 inches (457mm) minimum]
E = clearance to unventilated soffit [12 inches (305mm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly within
36 inches (914mm) horizontally from the center-line of the regulator
I = clearance to service regulator vent outlet [*72 inches (1829mm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12 inches (305mm)
minimum]
K = clearance to a mechanical air supply inlet [*72 inches (1829mm)
minimum]
L = † clearance above paved side-walk or a paved driveway located on
public property [*84 inches (2133mm) minimum]
M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡]
N = clearance above a roof shall extend a minimum of 24 inches (610mm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (457mm)
vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow
the current
National Fuel Gas Code, ANS Z223.1
Note: Local codes or regulations may require different clearances
A = 6" (152mm)
Inside Corner
V
B
E
V
B = 6" (152mm)
C = Maximum depth of 48" (1219mm) for
recessed location
D = Minimum width for back wall of
recessed location -
Combustible - 38" (965mm)
Noncombustible - 24" (610mm)
E = Clearance from corner in
recessed location-
Combustible - 6" (152mm)
Noncombustible - 2" (51mm)
Outside Corner Recessed Location
G
H
G = Combustible 24" (610mm)
Noncombustible 18" (457mm)
Balcony with No Side Wall
V
J
Combustible &
Noncombustible
H = 24" (610mm)
J = 20" (508mm)
Balcony with Perpendicular Side Wall
C
D
C
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Figure 10 - Minimum Clearances for Vent Terminations
GENERAL VENTING
Continued