Desa MDVFST Indoor Fireplace User Manual


 
6
106442
MDVFST DIRECT-VENT GAS FIREPLACE
®
WARNING: Read all instruc-
tions completely and thoroughly
before attempting installation. Fail-
ure to do so could result in serious
injury, property damage or loss of
life. Operation of improperly in-
stalled and maintained venting sys-
tem could result in serious injury,
property damage or loss of life.
WARNING: Seal all vent connec-
tions. Seal only the outer pipe con-
nections high temperature silicone
(600°F/316° C). Before joining elbows
and pipes, apply a bead of high
temperature silicone sealant (GE
RTV 106/Loctite RTV 81585) to the
male end of the elbow or pipe. High
temperature silicone must also be
used to reseal any connections after
maintenance to venting system.
NOTICE: Failure to follow these
instructions will void the warranty.
INSTALLATION PRECAUTIONS
Consult local building codes before beginning
the installation. The installer must make sure to
select the proper vent system for installation.
Before installing vent kit, the installer must read
this fireplace manual and vent kit instructions.
Only a qualified installer or service person
should install venting system. The installer
must follow these safety rules:
Wear gloves and safety glasses for
protection
Use extreme caution when using ladders
or when on roof tops
Be aware of electrical wiring locations
in walls and ceilings
The following actions will void the war-
ranty on your venting system:
Installation of any damaged venting
component
Unauthorized modification of the vent-
ing system
Installation of any component part not
manufactured or approved by DESA
International
Installation other than as instructed by
these instructions
VENTING
INSTALLATION
WARNING: This gas fireplace
and vent assembly must be
vented directly to the outside.
The venting system must NEVER
be attached to a chimney serving
a separate solid fuel burning ap-
pliance. Each gas appliance must
use a separate vent system. Do
not use common vent systems.
WARNING: Horizontal sections
of this vent system require a mini-
mum clearance of 2" from the top of
the vent pipe and 1" minimum to the
sides and bottom. Vertical sections
of this system require a minimum of
1" clearance to combustible materi-
als on all sides of the vent pipe.
INSTALLATION PLANNING
There are two basic types of direct-vent
installation:
Horizontal Termination
Vertical Termination
It is important to select the proper length of
vent pipe for the type of termination you
choose. It is also important to note the wall
thickness.
For Horizontal Termination: Select the
amount of vertical rise desired. The horizon-
tal run of venting must have 1/4" rise for
every 12" of run towards the termination.
A MDVGFK ground floor horizontal vent
kit is specifically designed for common
horizontal installations in manufactured
(mobile) homes. Additional horizontal in-
stallations are described on page 9. All vent
kits and components are listed on page 13.
NOTICE: Treatment of firestops
and construction of the chase may
vary from building type to building
type. These instructions are not
substitutes for the requirements
of local building codes. You must
follow all local building codes.
Note:
When installing in a chase, you should
insulate the chase as you would the outside
walls of your home. This is especially im-
portant in cold climates. Minimum clear-
ance between vent pipes and combustible
materials such as insulation is 1".
After framing the chase (see Framing on
page 4) install the vent system by following
the installation instructions.
Installing Vent System in a Chase
A chase is a vertical boxlike structure built
to enclose venting that runs along the out-
side of a building. A chase is not required for
such venting.
WARNING: Never run the vent
downward as this may cause ex-
cessive temperatures which
could cause a fire.
You may use one or two 90° elbows in a
horizontal vent configuration. See Horizon-
tal Termination Configurations on page 9.
For Vertical Termination: Measure the dis-
tance from the fireplace flue outlet to the
ceiling. Add the ceiling thickness, the verti-
cal rise in an attic or second story, and allow
for sufficient vent height above the roofline.
You may use one or two 90° elbows in a
vertical vent configuration. See Vertical Ter-
mination Configurations on pages 11 and 12.
Note:
You may use two 45° elbows in place
of a 90° elbow. You must follow rise to run
ratios when using 45° elbows.
The MDV9K 9' vertical vent kit is specifi-
cally designed for common vertical installa-
tions in manufactured (mobile) homes. Ad-
ditional vertical installations are described
on pages 11 and 12. All vent kits and com-
ponents are listed on page 13.
For two-story applications, firestops are re-
quired at each floor level. If an offset is
needed in the attic, additional pipe and el-
bows will be required.
You may use a chase with a vent termination
with exposed pipe on the exterior of the house.
See Installing Vent System in a Chase, below.
Your Vanguard direct-vent fireplace has
been tested for a minimum 3' rise with a
maximum 10" wall thickness. The maxi-
mum horizontal run is 20' with 8' vertical
rise (see Installation for Horizontal Termi-
nation, pages 7 through 9). The maximum
vertical run is 40' (see Installation for Ver-
tical Termination, page 10 through 12).
It is very important that the venting system
maintain its balance between the combus-
tion air intake and the flue gas exhaust.
Certain limitations apply to vent configura-
tions and must be strictly followed.