Desa (V)DVF36 Indoor Fireplace User Manual


 
www.desatech.com
56131-F 7
0"
36"
2"
Wall In Front Of Glass
36" Min.
Perpendicular
Wall 2" Min.
From Opening
Right Side
Surround
(0" Min.)
Left Side
Surround
(0" Min.)
TOP VIEW
Figure 6 - Mantel Clearances for
Peninsula and See-Thru Fireplaces
(Peninsula Shown)
21" Min.
15" Min.
12" Min.
4"
Min.
7" Min.
1
1
/
2
" Max.
UNIT
Spacer
2 x 4
Combustible
Material May
Be Used
Drywall (Gypsum
Board, Sheetrock, Etc.)
Safe Zone for
Projection of
Combustible
Material
Woodwork, such as wood trims, mantels and other
combustible materials should not be placed within
7" of the opening of this replace (see Figure 6).
Combustible material above projecting more than
1
1
/
2
" from the appliance’s front face must not be
placed less than 15" from the opening of the appli-
ance, (ref. NFPA Standard 211 Sec. 7-3.3.3)
PRE-INSTALLATION
PREPARATION
Continued
Figure 5 - Minimum Clearances
(See-Thru Shown)
Combustible Material
Drywall
2 x 4
Stud
Minimum 1" Clearance from
Side (Only for See-Thru)
FRAMING
Once the nal location has been determined, ob-
serving clearances for the vent termination, you
may construct framing using dimensions shown
in Figures 7 to 13 depending on your particular
installation
If the appliance is to be installed directly on carpeting,
tile (other than ceramic), or any combustible mate-
rial other than wood ooring, the appliance must be
installed upon a metal or wood panel extending the
full width and depth of the appliance. There are three
holes on each side of the bottom of the unit where
screws can be used to secure the unit to the oor.
The gas supply line may be connected through the
side framing or alternately through the lower sub-
ooring or a platform base if provided (see Figures
10 and 11, page 8). Depending on installation, refer
to appropriate illustrations.
Figure 7 - Rough Opening for Installing
Peninsula Fireplace
39
3
/
4
" Min.
40
1
/
2
"
23
5
/
8
"
39
3
/
4
"
Min.
40
1
/
2
"
23
5
/
8
"
*
Figure 8 - Rough Opening for Installing
Peninsula Fireplace on Platform
* As required by design as long as
ceiling clearance is maintained.
Platform
Must Be
Solid, Flat,
and Fully
Supported