Carrier 58PHA/PHX Furnace User Manual


 
21
Table 7 – Electrical Data
FURNACE
MODEL
VO LTS ---
HE R TZ ---
PHASE
OPERATING
VOLTAGE*
(VOLTS)
MAX UNIT
(AMPS)
UNIT
AMPACITY#
(AMPS)
MAX WIRE
LENGTH
}
FT.(M)
MAX FUSE/
CKT BKR
{
(AMPS)
MIN WIRE
GAGE
MAX MIN
045---08 / 024045 115 --- 60 --- 1 127 104 8.1 10.9 34 (10) 15 14
070---16 / 048070 115 --- 60 --- 1 127 104 9.5 12.6 29 (9) 15 14
090---16 / 048090 115 --- 60 --- 1 127 104 10.3 13.4 27 (8) 15 14
110---20 / 060110 115 --- 60 --- 1 127 104 13.1 16.9 34 (10) 20 12
135---20 / 060135 115 --- 60 --- 1 127 104 13.1 16.9 34 (10) 20 12
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unitampacity = 125 percent of largest operating component’s full load ampsplus 100 percent of all other potential operatingcomponents’ (EAC, humidifier,
etc.) ful l load amps.
{ Time---delay type is recommended.
} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
UNION
SEDIMENT
TRAP
MANUAL
SHUTOFF
VALVE
(REQUIRED)
GAS
SUPPLY
A02035
Fig. 22 -- Typical Gas Pipe Arrangement
ELECTRICAL
CONNECTIONS
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower access panel door switch opens 115--v power to
control. No component operation can occur. Do not bypass
or close switch with panel removed.
!
WARNING
See Fig. 25 for field wiring diagram showing typical field 115--v
wiring. Check all factory and field electrical connections for
tightness.
Field--supplied wiring shall conform with the limitations of 63_F
(35_C) rise.
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken
ground according to NEC ANSI/NFPA 70--2008 and
Canadian Electrical Code CSA C22.1 or local codes to
minimize personal injury if an electrical fault should occur.
This may consist of electrical wire, conduit approved for
electrical ground or a listed, grounded power cord (where
permitted by local code) when installed in accordance with
existing electrical codes. Refer to the power cord
manufacturer’s ratings for proper wire gauge. Do not use
gas piping as an electrical ground.
!
WARNING
58PHA