Table 6 — 50PSH, PSV, PSD Electrical Data, ECM Motor
LEGEND NOTES:
1. The 460-v units using an ECM (electronically commutated motor) fan
motor, modulating HWR, and/or an internal secondary pump will require
a neutral wire from the supply side in order to feed the accessory with
265-v.
2. Unit sizes 006-012 are not available with ECM motors.
50PS
UNIT
SIZE
RATED
VOLTAGE
V-Ph-Hz
VOLTAGE
MIN/MAX
COMPRESSOR
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE/
HACR
UNITS WITH ECM MOTOR AND HWR
RLA LRA Qty
REHEAT
PUMP
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE /
HACR
018
208/230-1-60 197/254 9.0 48.0 1 4.3 13.3 15.6 20 0.8 14.1 16.4 25
265-1-60 239/292 8.4 40.0 1 4.1 12.5 14.6 20 0.7 13.2 15.3 20
024
208/230-1-60 197/254 12.8 60.0 1 4.3 17.1 20.3 30 0.8 17.9 21.1 30
208/230-3-60 197/254 8.0 55.0 1 4.3 12.3 14.3 20 0.8 13.1 15.1 20
460-3-60 414/506 4.0 22.4 1 4.1 8.1 9.1 15 0.7 8.8 9.8 15
030
208/230-1-60 197/254 13.5 61.0 1 4.3 17.8 21.2 30 0.8 18.6 22.0 35
265-1-60 239/292 10.9 58.0 1 4.1 15.0 17.7 25 0.7 15.7 18.4 25
208/230-3-60 197/254 8.3 63.0 1 4.3 12.6 14.7 20 0.8 13.4 15.5 20
460-3-60 414/506 4.5 27.0 1 4.1 8.6 9.7 15 0.7 9.3 10.4 15
036
208/230-1-60 197/254 14.7 72.5 1 4.3 19.0 22.7 35 0.8 19.8 23.5 35
265-1-60 239/292 12.5 61.0 1 4.1 16.6 19.7 30 0.7 17.3 20.4 30
208/230-3-60 197/254 10.4 63.0 1 4.3 14.7 17.3 25 0.8 15.5 18.1 25
460-3-60 414/506 4.5 32.0 1 4.1 8.6 9.7 15 0.7 9.3 10.4 15
042
208/230-1-60 197/254 15.4 83.0 1 4.3 19.7 23.6 35 0.8 20.5 24.4 35
208/230-3-60 197/254 11.5 77.0 1 4.3 15.8 18.7 30 0.8 16.6 19.5 30
460-3-60 414/506 5.1 35.0 1 4.1 9.2 10.5 15 0.7 9.9 11.2 15
048
208/230-1-60 197/254 20.5 109.0 1 7.0 27.5 32.6 50 1.07 28.6 33.7 50
208/230-3-60 197/254 14.6 91.0 1 7.0 21.6 25.3 35 1.07 22.7 26.3 40
460-3-60 414/506 7.1 46.0 1 6.9 14.0 15.8 20 1.07 15.1 16.8 20
060
208/230-1-60 197/254 26.9 145.0 1 7.0 33.9 40.6 60 1.07 35.0 41.7 60
208/230-3-60 197/254 17.6 123.0 1 7.0 24.6 29.0 45 1.07 25.7 30.1 45
460-3-60 414/506 9.6 64.0 1 6.9 16.5 18.9 25 1.07 17.6 20.0 25
070
208/230-1-60 197/254 30.1 158.0 1 7.0 37.1 44.6 70 1.07 38.2 45.7 70
208/230-3-60 197/254 20.5 155.0 1 7.0 27.5 32.6 50 1.07 28.6 33.7 50
460-3-60 414/506 9.6 75.0 1 6.9 16.5 18.9 25 1.07 17.6 20.0 25
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
HWR Hot Water Reheat
LRA Locked Rotor Amps
RLA Rated Load Amps
COMPLETE C CONTROL
ECM CONTROL
BOARD
CAPACITOR
LINE
LOAD
COMPRESSOR CONTACTOR
TRANSFORMER
Fig. 26 — 50PSH,PSV,PSD Typical Single-Phase Line Voltage Power Connection