Carrier 50PSH Heat Pump User Manual


 
17
Wire Nut
Relay Contacts - N.C.
Relay Contacts - N.O.
Low Pressure Switch
High Pressure Switch
Splice Cap
Circuit Breaker
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. Transformer is wired to 460 v (BLK/RED) lead for 460/3/60
units. Transformer is energy limiting or may have circuit
breaker.
4. FP1 thermistor provides freeze protection for water. When
using antifreeze solutions, cut JW3 jumper.
5. Typical thermostat wiring shown. Refer to thermostat installa-
tion instructions for wiring to the unit. Thermostat wiring must
be Class 1 and voltage rating equal to or greater than unit sup-
ply voltage.
6. Factory cut JW1 jumper. Dry contact will be available between
AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs
and screws to control box. (Ground available from top two
standoffs as shown.)
8. Aquastat is supplied with unit and must be wired in series with
the hot leg to the pump. Aquastat is rated for voltages up to
277-v.
9. Optional LON wires. Only connect if LON connection is desired
at the wall sensor.
10. Fan motors are factory wired for medium speed. For high or low
speed, remove BLU wire from fan motor speed tap “M and
connect to “H for high speed or “L for low speed.
11. For low speed, remove BLK wire from BR “6 and replace with
RED. Connect BLK and BRN wires together.
12. For blower motors with leads. For medium or low speed,
disconnect BLK wire from BR “6. Connect BLK and ORG/PUR
wire together. Connect RED for low or BLU for medium to
BR “6.
13. The 460-v units using an ECM (electronically commutated
motor) fan motor, modulating HWR (hot water reheat), and/or
an internal secondary pump will require a neutral wire from the
supply side in order to feed the accessory with 265-v.
LEGEND
AL Alarm Relay Contacts
ASTAT Aquastat
BM Blower Motor
BMC Blower Motor Capacitor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
DTS Discharge Temperature Switch
ECM Electronically Commutated Motor
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HPWS High-Pressure Water Switch
HWG Hot Water Generator
JW1 Clippable Field Selection Jumper
LOC Loss of Charge Pressure Switch
LON Local Operating Network
MV Motorized Valve
MVES Motorized Valve End Switch
*Optional Wiring.
NEC National Electrical Code
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS Transformer
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Condensate Pan
Solenoid Coil
Temperature Switch
Thermistor
Ground
Complete C
a50-8363
Fig 18 — Units with ECM, Complete C and LON Controller (460 V)