Table 7 Fan Performance, 48TJ008 Vertical Discharge Units
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2200 506 0.52 586 0.72 656 0.95 718 1.18 776 1.43 838 1.78 898 2.21 935 2.58
2250 514 0.55 593 0.76 662 0.99 724 1.22 781 1.78 841 1.81 902 2.25 939 2.60
2300 521 0.57 600 0.79 668 1.02 730 1.26 786 1.50 843 1.83 905 2.28 943 2.62
2400 536 0.63 613 0.85 680 1.09 741 1.34 796 1.59 849 1.88 910 2.31 952 2.74
2500 551 0.69 626 0.93 693 1.17 753 1.43 808 1.69 859 1.96 912 2.31 963 2.81
2550 559 0.72 634 0.97 700 1.21 759 1.48 814 1.74 864 2.01 915 2.34 968 2.81
2600 567 0.75 641 1.00 706 1.25 764 1.52 819 1.79 869 2.06 918 2.37 973 2.81
2700 582 0.83 655 1.08 719 1.34 776 1.61 831 1.89 880 2.17 927 2.47 976 2.84
2800 598 0.90 670 1.17 732 1.43 789 1.71 842 2.00 892 2.29 938 2.58 983 2.92
2900 614 0.98 684 1.25 745 1.53 802 1.81 854 2.11 903 2.42 949 2.71 993 3.03
3000 630 1.07 699 1.35 759 1.63 815 1.92 866 2.23 915 2.54 961 2.85 1003 3.17
3100 646 1.16 714 1.45 773 1.74 828 2.04 878 2.35 926 2.67 972 3.00 1015 3.32
3200 662 1.26 729 1.55 787 1.86 841 2.16 891 2.48 938 2.81 983 3.14 1026 3.47
3300 679 1.36 744 1.66 801 1.98 854 2.29 904 2.61 950 2.95 995 3.30
3400 695 1.47 759 1.78 816 2.10 867 2.42 917 2.75 963 3.10 1007 3.45
3500 712 1.59 774 1.90 830 2.23 881 2.56 930 2.90 976 3.25 ————
3600 729 1.71 790 2.03 845 2.37 895 2.71 943 3.05 988 3.41 ————
3700 745 1.84 805 2.17 860 2.52 909 2.87 956 3.22 —————
3750 754 1.91 813 2.24 868 2.59 917 2.95 963 3.30 —————
LEGEND
Bhp Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 4.)
2. indicates alternate drive required.
3. indicates field-supplied motor and drive required.
4. Standard drive range is 590 to 840 rpm. Alternate drive range is
685 to 935 rpm. All other rpms require a field-supplied drive.
5. Values include losses for filters, unit casing, and wet coils.
6. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the rat-
ings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected.
7. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
8. Interpolation is permissible. Do not extrapolate.
Table 8 Fan Performance, 48TJ009 Vertical Discharge Units
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2550 559 0.72 634 0.97 700 1.21 759 1.48 814 1.74 864 2.01 915 2.34 968 2.81
2600 567 0.75 641 1.00 706 1.25 764 1.52 819 1.79 869 2.06 918 2.37 973 2.81
2700 582 0.83 655 1.08 719 1.34 776 1.61 831 1.89 880 2.17 927 2.47 976 2.84
2800 598 0.90 670 1.17 732 1.43 789 1.71 842 2.00 892 2.29 938 2.58 983 2.92
2900 614 0.98 684 1.25 745 1.53 802 1.81 854 2.11 903 2.42 949 2.71 993 3.03
3000 630 1.07 690 1.35 759 1.63 815 1.92 866 2.23 915 2.54 961 2.85 1003 3.17
3100 646 1.16 714 1.45 773 1.74 828 2.04 878 2.35 926 2.67 972 3.00 1016 3.32
3200 662 1.26 729 1.55 787 1.86 841 2.16 891 2.48 938 2.81 983 3.14 1026 3.47
3300 679 1.36 744 1.66 801 1.98 854 2.29 904 2.61 950 2.95 995 3.30
3400 695 1.47 759 1.78 816 2.10 867 2.42 917 2.75 963 3.10 1007 3.45
3500 712 1.59 774 1.90 830 2.23 881 2.56 930 2.90 976 3.25 ————
3600 729 1.71 790 2.03 845 2.37 895 2.71 943 3.05 988 3.41 ————
3700 745 1.84 805 2.17 860 2.52 909 2.87 956 3.22 —————
3750 754 1.91 813 2.24 868 2.59 917 2.95 963 3.30 —————
3800 762 1.98 821 2.31 875 2.66 924 3.03 970 3.38 —————
3900 779 2.12 836 2.46 890 2.82 938 3.19 ————————
4000 796 2.27 852 2.61 905 2.98 953 3.37 ————————
4100 813 2.42 868 2.78 920 3.15 ——————————
4200 830 2.59 884 2.95 935 3.33 ——————————
4250 839 2.68 890 3.04 ————————————
4300 847 2.76 900 3.13 ————————————
LEGEND
Bhp Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Standard drive range is 685 to 935 rpm. All other rpms require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Maximum continuous bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the rat-
ings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. Interpolation is permissible. Do not extrapolate.
19