Carrier 48TJD008-014 Air Conditioner User Manual


 
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INSTALLATION .............................1-22
Step 1 Provide Unit Support ...............1
ROOF CURB
SLAB MOUNT
Step 2 Field Fabricate Ductwork ............2
Step 3 Install External Trap for
Condensate Drain ..........................2
Step 4 Rig and Place Unit ..................2
POSITIONING
Step 5 Install Flue Hood ...................8
Step 6 Install Gas Piping ...................8
Step 7 Make Electrical Connections ........8
FIELD POWER SUPPLY
FIELD CONTROL WIRING
HEAT ANTICIPATOR SETTINGS
Step 8 Adjust Factory-Installed Options ...11
APOLLO CONTROL
MANUAL OUTDOOR-AIR DAMPER
OPTIONAL DURABLADE ECONOMIZER
OPTIONAL PARABLADE ECONOMIZER
Step 9 Adjust Evaporator-Fan Speed ......16
START-UP .................................23,24
SERVICE ..................................25-30
TROUBLESHOOTING ......................31-36
START-UP CHECKLIST .................... CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical com-
ponents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, ob-
serve precautions in the literature, tags and labels attached
to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire ex-
tinguishers available for all brazing operations.
Disconnect gas piping from unit when leak
testing at pressure greater than
1
2
psig. Pres-
sures greater than
1
2
psig will cause gas
valve damage resulting in hazardous con-
dition. If gas valve is subjected to pres-
sure greater than
1
2
psig, it must be replaced
before use. When pressure testing field-
supplied gas piping at pressures of
1
2
psig
or less, a unit connected to such piping must
be isolated by manually closing the gas
valve(s).
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
INSTALLATION
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same screws,
install covers on vertical duct openings with the insulation-
side down. Seals around duct openings must be tight. See
Fig. 1.
Step 1 Provide Unit Support
ROOF CURB Assemble and install accessory roof curb
in accordance with instructions shipped with curb. See
Fig. 2. Install insulation, cant strips, roofing felt, and counter
flashing as shown. Ductwork must be attached to curb. If
gas is to be routed through the curb, attach the accessory
thru-the-curb service connection plate to the roof curb in ac-
cordance with the accessory installation instructions. Con-
nection plate must be installed before unit is set in roof curb.
IMPORTANT: The gasketing of the unit to the roof
curb is critical for a watertight seal. Install gasket sup-
plied with the roof curb as shown in Fig. 2. Improp-
erly applied gasket can also result in air leaks and poor
unit performance.
Curb should be level. Unit leveling tolerances are shown
in Fig. 3. This is necessary for unit drain to function prop-
erly. Refer to Accessory Roof Curb Installation Instructions
for additional information as required.