RTU Open 69
Point Name/Description
Default/Range
Fire Shutdown
–
Shutdown
R: indicates that a fire shutdown is in effect. Run Enabled/
Shutdown
Compressor Safety Status
–
Trouble
R: indicates that the compressor safety device has
tripped.
Normal/Trouble
Enthalpy Status
R: – The enthalpy status determined by an enthalpy switch. High/Low
Humidistat Input Status
R: – The humidity status determined by a humidistat. High/Low
Reset Supply Fan Runtime Alarm
– Set to
Clear
to reset
Supply Fan Runtime
D: to 0.
R:
Run
Run/Clear
Reset Comp 1 Runtime Alarm
– Set to
Clear
to reset
Compressor 1 Runtime
D: to 0.
R:
Run
Run/Clear
Reset Comp 2 Runtime Alarm
– Set to
Clear
to reset
Compressor 2 Runtime
D: to 0.
R:
Run
Run/Clear
Reset Filter Runtime Alarm
– Set to
On
to reset
Filter Runtime
D: to 0.
R:
Off
Off/On
Occupancy
BAS On/Off
Options:
– Determines the occupancy state of the controller and can be set over the
network by another device or third party BAS.
Inactive
– Occupancy is determined by a configured schedule.
Occupied
– The controller is always in the occupied mode.
Unoccupied
D:
– The controller is always in the unoccupied mode.
R:
Inactive
Inactive
Occupied
Unoccupied
Schedules
R: – The controller's occupancy status based on the schedule. Occupied/Unoccupied
Pushbutton Override
–
Active
R:
indicates if a user pushed the sensor's override button to
override the occupancy state.
Off/Active
Override Time Remaining
R:
– The amount of time remaining in an override period. 0 to 240 minutes
Runtime
Supply Fan Runtime
– The total number of hours that the supply fan relay has been
energized since the runtime was last reset to 0 using
Reset Supply Fan Runtime Alarm
R:
.
___ hr
Compressor 1 Runtime
– The total number of hours that the Compressor 1 relay has
been energized since the runtime was last reset 0 using
Reset Comp 1 Runtime Alarm
R:
.
___ hr
Compressor 2 Runtime
– The total number of hours that the Compressor 2 relay has
been energized since the runtime was last reset using
Reset Comp 2 Runtime Alarm
R:
.
___ hr
Filter Runtime
– The total number of hours that the unit has been operating since the
runtime was last reset to 0 using
Reset Filter Runtime Alarm
R:
.
___ hr