Carrier 11-808-427-01 Air Conditioner User Manual


 
Appendix A: RTU Open Points/Properties
58 RTU Open
Status
Navigation: i-Vu / Field Assistant:
BACview:
Properties
>
Equipment
>
Status
HOME > STATUS
Point Name/Description
Range
System Mode
R: The controller's current operating status. Disabled
Test
Run
Operating Mode
R: The controller's current operating mode. Off
Fan Only
Economizer
Cooling
Heating
Dehumidification
Test
Shutdown
Unocc Free Cooling (NTFC)
Supply Fan Status
The current fan status if an input is configured for
Fan Status
R: . Off/Running
Space Temperature
- Prime Variable
R: The space temperature value currently used for
control.
-56 to 245°F
Supply Air Temperature
R: The current supply air temperature. -56 to 245°F
Outdoor Air Temperature
R: The outdoor air temperature value used for control. -56 to 245°F
Space Relative Humidity
– The current space relative humidity if
Configuration
>
Unit
Configuration
>
Input 1
(or
2
)
Function
is set to
Space RH Sensor
R:
.
0 to 100%rh
Indoor Air CO2
The current indoor air CO
2
concentration if the
Configuration
>
Unit
Configuration
>
Input 1
(or
2
)
Function
is set to
IAQ Sensor
R:
.
0 to 5000ppm
Outdoor Air CO2
The current outdoor air CO
2
concentration if the
Configuration
>
Unit
Configuration
>
Input 1
(or
2
)
Function
is set to
OAQ Sensor
R:
.
0 to 5000ppm
Economizer Output
R: The current economizer output with respect to the outdoor air
damper (if equipped).
0 to 100% Open
Appendix A: RTU Open Points/Properties