Carrier 11-808-427-01 Air Conditioner User Manual


 
RTU Open 39
Point Name/Description
Default/Range
Input 9
Switch Configuration
D: The normal (de-energized) state for the set of contacts
terminated at Input
R:
NO
NO/NC (normally
open/normally closed)
Space sensor type
D: - The type of local space temperature sensor.
R:
T55
T55
T56 (Use for T59)
SPT Sensor
None
Setpoint properties
i-Vu / Field Assistant:
Navigation:
BACview:
Properties
>
Equipment
>
Configuration
>
Setpoints
HOME > CONFIG > SETPOINT
Select a color band on the setpoint graph to see the current setpoints in the
Heating
and
Cooling
fields. See setpoint
descriptions below.
Point Name/Description
Default/Range
Occupied Heating
D: – Green
The heating setpoint the controller maintains while in occupied mode.
R:
70°F
-40 to 245°F
Occupied Cooling
D: – Green
The cooling setpoint the controller maintains while in occupied mode.
R:
74°F
-40 to 245°F
Unoccupied Heating
D: Gray
The heating setpoint the controller maintains while in unoccupied mode.
R:
55°F
45 to 100°F
Unoccupied Cooling
D: Gray
The cooling setpoint the controller maintains while in unoccupied mode.
R:
90°F
-40 to 245°F