Carrier 11-808-427-01 Air Conditioner User Manual


 
Installation
20 RTU Open
Wiring an SPT sensor
The RTU Open is connected to a wall-mounted space temperature sensor to monitor room temperature.
An i-Vu Open Control System offers the following SPT sensors:
Sensor
Part #
Features
SPS
SPT Standard
Local access port
No operator control
SPPL
SPT Plus
Slide potentiometer to adjust setpoint
MANUAL ON button to override schedule
LED to show occupied status
Local access port
SPP
SPT Pro
LCD display
MANUAL ON button to override schedule
WARMER and COOLER buttons to adjust setpoint
INFO button to cycle through zone and outside air temperatures,
setpoints, and local override time
Local access port
You wire SPT sensors to the RTU Open's Rnet port. An Rnet can consist of any of the following combinations
of devices wired in a daisy-chain configuration:
1 SPT Plus or SPT Pro
1–4 SPT Standards
1–4 SPT Standards, and 1 SPT Plus or SPT Pro
Any of the above combinations, plus up to 2 BACview
6
NOTES
's but no more than 6 devices total
If you have 2 BACview
6
's, the second BACview
6
must have a separate power supply with the same
ground as the controller.
If the Rnet has multiple SPT Standard sensors, you must give each a unique address on the Rnet. See
the Carrier Sensors Installation Guide.
If the Rnet has multiple BACviews, you must give each a unique address on the Rnet. See the BACview
Installation and User Guide.
Rnet wiring specifications
NOTE Use the specified type of wire and cable for maximum signal integrity.
Description 4 conductor, unshielded, CMP, plenum rated cable
Conductor 18 AWG
Maximum length 500 feet (152 meters)
Recommended coloring Jacket: White
Wiring: Black, white, green, red
UL temperature rating 32–167°F (0–75°C)