Performance Data — GT-PG Model 060 - ECM Blower
1,825 CFM Nominal (Rated) Air ow Cooling, 2,050 CFM Nominal (Rated) Air ow Heating Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Air ow
CFM
TC SC kW HR EER HW
Air ow
CFM
HC kW HE LAT COP HW
20
15.0 5.0 11.6
N/A N/A N/A N/A N/A N/A N/A 1470 39.6 4.02 26.6 95 2.89 2.8
15.0 5.0 11.6
N/A N/A N/A N/A N/A N/A N/A 2050 40.9 3.72 28.3 88 3.22 2.9
30
7.5 0.6 1.4 1320 62.0 37.7 2.30 69.7 26.9 0.7 1470 42.9 4.09 29.5 97 3.07 3.5
7.5 0.6 1.4 1825 64.4 43.9 2.44 72.7 26.5 0.8 2050 44.2 3.78 31.4 90 3.42 3.6
11.3 2.3 5.3 1320 63.4 38.5 2.32 71.2 27.4 0.7 1470 44.5 4.13 31.0 98 3.16 3.6
11.3 2.3 5.3 1825 65.9 44.8 2.45 74.2 26.9 0.7 2050 45.9 3.82 33.0 91 3.52 3.7
15.0 4.8 11.1 1320 65.6 39.8 2.27 73.2 28.9 0.6 1470 45.4 4.15 31.8 99 3.21 3.7
15.0 4.8 11.1 1825 68.2 46.3 2.40 76.4 28.4 0.7 2050 46.8 3.83 33.8 91 3.58 3.8
40
7.5 0.5 1.2 1320 65.6 40.3 2.57 74.2 25.5 1.5 1470 48.6 4.21 34.7 101 3.38 4.0
7.5 0.5 1.2 1825 68.2 46.9 2.72 77.4 25.1 1.5 2050 50.1 3.89 36.9 93 3.77 4.1
11.3 2.2 5.1 1320 66.3 40.5 2.49 74.7 26.6 1.3 1470 50.7 4.25 36.6 102 3.49 4.2
11.3 2.2 5.1 1825 69.0 47.1 2.64 77.9 26.1 1.4 2050 52.2 3.93 38.9 94 3.90 4.3
15.0 4.5 10.4 1320 67.1 40.9 2.45 75.3 27.4 1.2 1470 51.8 4.27 37.7 103 3.55 4.3
15.0 4.5 10.4 1825 69.8 47.6 2.59 78.6 26.9 1.2 2050 53.4 3.95 40.0 94 3.96 4.5
50
7.5 0.4 0.9 1320 66.5 41.3 2.84 76.0 23.4 2.5 1470 54.7 4.33 40.3 104 3.70 4.6
7.5 0.4 0.9 1825 69.1 48.1 3.00 79.3 23.0 2.6 2050 56.4 4.00 42.8 95 4.13 4.7
11.3 2.1 4.9 1320 67.2 41.4 2.69 76.2 25.0 2.2 1470 57.2 4.38 42.6 106 3.83 4.8
11.3 2.1 4.9 1825 69.9 48.2 2.85 79.5 24.5 2.3 2050 59.0 4.04 45.3 97 4.28 4.9
15.0 4.3 9.9 1320 68.1 41.9 2.62 76.9 26.0 2.0 1470 58.7 4.40 43.9 107 3.90 5.0
15.0 4.3 9.9 1825 70.8 48.7 2.77 80.2 25.5 2.0 2050 60.5 4.07 46.6 97 4.36 5.1
60
7.5 0.3 0.7 1320 65.3 41.3 3.11 75.8 21.0 3.5 1470 61.0 4.45 46.0 108 4.02 5.2
7.5 0.3 0.7 1825 67.9 48.0 3.29 79.1 20.6 3.6 2050 62.9 4.11 48.9 98 4.49 5.4
11.3 2.1 4.9 1320 66.5 41.6 2.93 76.4 22.7 3.1 1470 64.0 4.50 48.7 110 4.16 5.4
11.3 2.1 4.9 1825 69.1 48.4 3.09 79.7 22.3 3.2 2050 66.0 4.16 51.8 100 4.65 5.6
15.0 4.1 9.5 1320 66.9 41.6 2.84 76.5 23.6 2.7 1470 65.6 4.54 50.2 111 4.24 5.6
15.0 4.1 9.5 1825 69.6 48.4 3.00 79.8 23.2 2.8 2050 67.6 4.19 53.3 101 4.73 5.8
70
7.5 0.3 0.7 1320 63.4 40.7 3.35 74.7 18.9 4.7 1470 66.1 4.55 50.7 112 4.26 5.9
7.5 0.3 0.7 1825 65.9 47.4 3.54 77.9 18.6 4.9 2050 68.2 4.20 53.8 101 4.76 6.0
11.3 2.0 4.6 1320 64.6 41.1 3.20 75.4 20.2 4.2 1470 70.7 4.64 54.8 115 4.47 6.1
11.3 2.0 4.6 1825 67.2 47.8 3.38 78.7 19.9 4.4 2050 72.9 4.28 58.2 103 4.98 6.3
15.0 3.9 9.0 1320 65.4 41.3 3.10 75.9 21.1 3.7 1470 72.4 4.67 56.4 116 4.54 6.3
15.0 3.9 9.0 1825 68.0 48.1 3.28 79.1 20.8 3.9 2050 74.7 4.32 59.9 104 5.07 6.5
80
7.5 0.2 0.5 1320 59.7 39.5 3.76 72.5 15.9 5.7 1470 73.6 4.70 57.4 116 4.59 6.4
7.5 0.2 0.5 1825 62.1 46.0 3.98 75.6 15.6 5.9 2050 75.9 4.34 61.0 104 5.12 6.6
11.3 1.9 4.4 1320 61.9 40.2 3.52 73.8 17.6 5.3 1470 77.0 4.77 60.5 119 4.73 6.7
11.3 1.9 4.4 1825 64.3 46.8 3.72 77.0 17.3 5.5 2050 79.4 4.41 64.3 106 5.28 6.9
15.0 3.6 8.3 1320 62.9 40.6 3.40 74.4 18.5 4.8 1470 78.8 4.81 62.1 120 4.80 6.9
15.0 3.6 8.3 1825 65.4 47.2 3.60 77.6 18.2 5.0 2050 81.3 4.45 66.0 107 5.36 7.1
85
7.5 0.2 0.5 1320 57.9 38.9 3.96 71.4 14.6 6.4 1470 76.5 4.76 60.1 118 4.71 6.7
7.5 0.2 0.5 1825 60.2 45.3 4.19 74.5 14.4 6.7 2050 78.9 4.40 63.8 106 5.25 6.9
11.3 1.9 4.3 1320 60.2 39.7 3.70 72.8 16.3 5.9 1470 79.9 4.84 63.1 120 4.84 7.0
11.3 1.9 4.3 1825 62.6 46.2 3.92 75.9 16.0 6.2 2050 82.4 4.47 67.1 107 5.40 7.2
15.0 3.6 8.2 1320 61.3 40.0 3.58 73.5 17.1 5.4 1470 81.7 4.89 64.7 121 4.90 7.3
15.0 3.6 8.2 1825 63.7 46.6 3.79 76.6 16.8 5.7 2050 84.2 4.51 68.7 108 5.47 7.4
90
7.5 0.2 0.5 1320 56.2 38.3 4.17 70.4 13.5 7.4 1470 79.4 4.83 62.7 120 4.82 7.0
7.5 0.2 0.5 1825 58.4 44.5 4.41 73.4 13.2 7.6 2050 81.9 4.46 66.6 107 5.38 7.2
11.3 1.8 4.2 1320 58.5 39.1 3.89 71.8 15.0 6.8 1470 82.8 4.91 65.7 122 4.94 7.3
11.3 1.8 4.2 1825 60.8 45.5 4.12 74.9 14.8 7.1 2050 85.4 4.54 69.8 109 5.51 7.5
15.0 3.5 8.1 1320 59.7 39.5 3.76 72.5 15.9 6.2 1470 84.5 4.96 67.2 123 5.00 7.6
15.0 3.5 8.1 1825 62.1 46.0 3.98 75.6 15.6 6.5 2050 87.1 4.58 71.4 109 5.57 7.8
100
7.5 0.1 0.2 1320 52.4 37.0 4.64 68.3 11.3 8.1
N/A N/A N/A N/A N/A N/A
7.5 0.1 0.2 1825 54.5 43.1 4.91 71.3 11.1 8.4
N/A N/A N/A N/A N/A N/A
11.3 1.8 4.2 1320 54.8 37.8 4.33 69.6 12.7 7.8
N/A N/A N/A N/A N/A N/A
11.3 1.8 4.2 1825 57.0 44.0 4.58 72.6 12.4 8.1
N/A N/A N/A N/A N/A N/A
15.0 3.3 7.6 1320 56.0 38.2 4.18 70.3 13.4 7.5
N/A N/A N/A N/A N/A N/A
15.0 3.3 7.6 1825 58.3 44.5 4.42 73.4 13.2 7.8
N/A N/A N/A N/A N/A N/A
110
7.5 0.1 0.2 1320 48.6 35.8 5.20 66.5 9.3 9.7
N/A N/A N/A N/A N/A N/A
7.5 0.1 0.2 1825 50.5 41.6 5.50 69.4 9.2 10.1
N/A N/A N/A N/A N/A N/A
11.3 1.7 3.9 1320 50.9 36.5 4.85 67.6 10.5 9.4
N/A N/A N/A N/A N/A N/A
11.3 1.7 3.9 1825 53.0 42.5 5.13 70.5 10.3 9.7
N/A N/A N/A N/A N/A N/A
15.0 3.1 7.2 1320 52.2 36.9 4.68 68.2 11.2 9.0
N/A N/A N/A N/A N/A N/A
15.0 3.1 7.2 1825 54.2 43.0 4.95 71.1 11.0 9.4
N/A N/A N/A N/A N/A N/A
120
7.5 0.0 0.0 1320 45.1 34.8 5.85 65.3 7.7 11.5
N/A N/A N/A N/A N/A N/A
7.5 0.0 0.0 1825 46.9 40.5 6.19 68.1 7.6 12.0
N/A N/A N/A N/A N/A N/A
11.3 1.7 3.9 1320 47.2 35.4 5.45 65.9 8.7 11.1
N/A N/A N/A N/A N/A N/A
11.3 1.7 3.9 1825 49.1 41.1 5.76 68.8 8.5 11.6
N/A N/A N/A N/A N/A N/A
15.0 2.9 6.7 1320 48.3 35.7 5.25 66.4 9.2 10.7
N/A N/A N/A N/A N/A N/A
15.0 2.9 6.7 1825 50.2 41.5 5.56 69.2 9.0 11.1
N/A N/A N/A N/A N/A N/A
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not re ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Operation not recommended
Operation not recommended