Bryant GT-PG (50YE) Heating System User Manual


 
Bryant Geothermal Heat Pump Systems
GT-PG
25
Residential Products Technical Guide
Performance Data — GT-PG Model 060 - PSC Blower
1,950 CFM Nominal (Rated) Air ow Cooling, 1,950 CFM Nominal (Rated) Air ow Heating Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Air ow
CFM
TC SC kW HR EER HW
Air ow
CFM
HC kW HE LAT COP HW
20
15.0 5.0 11.6
N/A N/A N/A N/A N/A N/A N/A 1465 40.8 4.43 26.6 96 2.70 2.8
15.0 5.0 11.6
N/A N/A N/A N/A N/A N/A N/A 1950 41.9 4.05 28.2 90 3.03 2.9
30
7.5 0.6 1.4 1465 61.8 36.2 2.64 70.8 23.4 0.8 1465 44.1 4.50 29.6 98 2.88 3.4
7.5 0.6 1.4 1950 64.3 43.4 2.73 73.6 23.6 0.8 1950 45.3 4.11 31.4 92 3.23 3.5
11.3 2.3 5.3 1465 63.0 36.5 2.63 72.0 23.9 0.7 1465 45.8 4.53 31.1 99 2.96 3.5
11.3 2.3 5.3 1950 65.6 43.7 2.72 74.9 24.1 0.8 1950 47.0 4.14 33.0 92 3.33 3.6
15.0 4.8 11.1 1465 64.9 37.4 2.60 73.8 24.9 0.7 1465 46.7 4.55 32.0 100 3.01 3.7
15.0 4.8 11.1 1950 67.6 44.8 2.69 76.7 25.1 0.7 1950 48.0 4.16 33.9 93 3.38 3.8
40
7.5 0.5 1.2 1465 64.9 38.6 2.86 74.6 22.7 1.5 1465 50.0 4.61 34.9 102 3.18 4.0
7.5 0.5 1.2 1950 67.5 46.2 2.96 77.6 22.9 1.6 1950 51.3 4.22 37.0 94 3.57 4.1
11.3 2.2 5.1 1465 65.4 38.7 2.76 74.9 23.7 1.4 1465 52.1 4.65 36.8 103 3.28 4.1
11.3 2.2 5.1 1950 68.2 46.3 2.85 77.8 23.9 1.5 1950 53.5 4.25 39.1 95 3.69 4.2
15.0 4.5 10.4 1465 66.0 38.8 2.72 75.3 24.3 1.3 1465 53.3 4.67 37.9 104 3.34 4.3
15.0 4.5 10.4 1950 68.8 46.4 2.81 78.3 24.5 1.3 1950 54.7 4.27 40.2 96 3.75 4.4
50
7.5 0.4 0.9 1465 65.4 39.8 3.15 76.2 20.8 2.6 1465 56.1 4.73 40.5 105 3.48 4.5
7.5 0.4 0.9 1950 68.1 47.6 3.26 79.2 20.9 2.7 1950 57.6 4.32 43.0 97 3.91 4.7
11.3 2.1 4.9 1465 66.1 39.8 2.97 76.2 22.2 2.3 1465 58.7 4.77 42.9 107 3.60 4.7
11.3 2.1 4.9 1950 68.8 47.6 3.07 79.2 22.4 2.4 1950 60.3 4.37 45.5 99 4.05 4.8
15.0 4.3 9.9 1465 66.4 39.8 2.91 76.3 22.9 2.1 1465 60.1 4.80 44.1 108 3.67 4.9
15.0 4.3 9.9 1950 69.2 47.6 3.00 79.4 23.0 2.1 1950 61.7 4.39 46.8 99 4.12 5.0
60
7.5 0.3 0.7 1465 64.0 39.9 3.50 76.0 18.3 3.6 1465 62.5 4.84 46.3 109 3.78 5.1
7.5 0.3 0.7 1950 66.7 47.8 3.62 79.0 18.4 3.8 1950 64.2 4.43 49.1 100 4.24 5.3
11.3 2.1 4.9 1465 65.3 40.1 3.26 76.4 20.0 3.3 1465 65.5 4.90 49.0 111 3.92 5.4
11.3 2.1 4.9 1465 65.3 40.1 3.26 76.4 20.0 3.4 1465 65.5 4.90 49.0 111 3.92 5.5
15.0 4.1 9.5 1465 65.7 40.1 3.17 76.5 20.7 2.9 1465 67.1 4.93 50.5 112 3.99 5.6
15.0 4.1 9.5 1950 68.4 48.0 3.27 79.5 20.9 3.0 1950 68.9 4.51 53.5 103 4.48 5.7
70
7.5 0.3 0.7 1465 61.6 39.2 3.84 74.7 16.0 5.0 1465 68.9 4.97 52.0 114 4.06 5.8
7.5 0.3 0.7 1950 64.2 46.9 3.97 77.7 16.2 5.2 1950 70.7 4.54 55.2 104 4.56 5.9
11.3 2.0 4.6 1465 63.4 39.7 3.61 75.7 17.6 4.4 1465 72.2 5.03 55.0 116 4.20 6.0
11.3 2.0 4.6 1950 66.0 47.6 3.73 78.7 17.7 4.6 1950 74.1 4.60 58.4 105 4.72 6.2
15.0 3.9 9.0 1465 64.1 39.9 3.49 76.1 18.4 3.9 1465 73.9 5.07 56.6 117 4.28 6.2
15.0 3.9 9.0 1950 66.8 47.8 3.61 79.1 18.5 4.1 1950 75.9 4.63 60.1 106 4.80 6.4
80
7.5 0.2 0.5 1465 58.6 38.1 4.23 73.1 13.9 6.0 1465 75.1 5.09 57.7 117 4.32 6.3
7.5 0.2 0.5 1950 61.1 45.6 4.37 76.0 14.0 6.2 1950 77.1 4.65 61.2 107 4.85 6.5
11.3 1.9 4.4 1465 60.7 38.9 3.96 74.2 15.3 5.5 1465 78.6 5.16 60.8 120 4.46 6.6
11.3 1.9 4.4 1950 63.2 46.6 4.09 77.2 15.4 5.8 1950 80.7 4.72 64.5 108 5.01 6.8
15.0 3.6 8.3 1465 61.7 39.2 3.83 74.8 16.1 5.1 1465 80.4 5.21 62.5 121 4.53 6.8
15.0 3.6 8.3 1950 64.3 47.0 3.96 77.8 16.2 5.3 1950 82.6 4.76 66.3 109 5.08 7.0
85
7.5 0.2 0.5 1465 56.9 37.4 4.44 72.1 12.8 6.8 1465 78.1 5.15 60.4 119 4.44 6.6
7.5 0.2 0.5 1950 59.3 44.8 4.59 75.0 12.9 7.0 1950 80.1 4.71 64.0 108 4.98 6.8
11.3 1.9 4.3 1465 59.1 38.3 4.16 73.3 14.2 6.2 1465 81.6 5.23 63.5 122 4.57 6.9
11.3 1.9 4.3 1950 61.6 45.8 4.30 76.3 14.3 6.5 1950 83.7 4.79 67.4 110 5.13 7.1
15.0 3.6 8.2 1465 60.2 38.7 4.03 73.9 14.9 5.7 1465 83.4 5.28 65.1 123 4.63 7.1
15.0 3.6 8.2 1950 62.7 46.3 4.17 76.9 15.0 6.0 1950 85.6 4.83 69.1 111 5.20 7.3
90
7.5 0.2 0.5 1465 55.2 36.8 4.66 71.2 11.9 7.7 1465 81.0 5.22 63.0 121 4.55 6.9
7.5 0.2 0.5 1950 57.5 44.0 4.82 74.0 11.9 8.0 1950 83.2 4.77 66.9 109 5.11 7.1
11.3 1.8 4.2 1465 57.5 37.7 4.37 72.4 13.2 7.1 1465 84.5 5.30 66.2 123 4.67 7.2
11.3 1.8 4.2 1950 59.9 45.1 4.51 75.3 13.3 7.4 1950 86.8 4.85 70.2 111 5.25 7.4
15.0 3.5 8.1 1465 58.6 38.1 4.23 73.1 13.9 6.6 1465 86.3 5.35 67.7 125 4.73 7.5
15.0 3.5 8.1 1950 61.1 45.6 4.37 76.0 14.0 6.8 1950 88.6 4.89 71.9 112 5.31 7.6
100
7.5 0.1 0.2 1465 51.7 35.3 5.15 69.3 10.0 8.5
N/A N/A N/A N/A N/A N/A
7.5 0.1 0.2 1950 53.9 42.3 5.32 72.1 10.1 8.8
N/A N/A N/A N/A N/A N/A
11.3 1.8 4.2 1465 54.0 36.3 4.83 70.5 11.2 8.2
N/A N/A N/A N/A N/A N/A
11.3 1.8 4.2 1950 56.2 43.4 4.99 73.3 11.3 8.5
N/A N/A N/A N/A N/A N/A
15.0 3.3 7.6 1465 55.2 36.7 4.67 71.1 11.8 7.9
N/A N/A N/A N/A N/A N/A
15.0 3.3 7.6 1950 57.5 44.0 4.83 74.0 11.9 8.2
N/A N/A N/A N/A N/A N/A
110
7.5 0.1 0.2 1465 48.2 33.8 5.70 67.7 8.5 10.2
N/A N/A N/A N/A N/A N/A
7.5 0.1 0.2 1950 50.2 40.5 5.89 70.4 8.5 10.6
N/A N/A N/A N/A N/A N/A
11.3 1.7 3.9 1465 50.4 34.8 5.35 68.7 9.4 9.9
N/A N/A N/A N/A N/A N/A
11.3 1.7 3.9 1950 52.5 41.6 5.53 71.4 9.5 10.3
N/A N/A N/A N/A N/A N/A
15.0 3.1 7.2 1465 51.5 35.2 5.18 69.2 10.0 9.5
N/A N/A N/A N/A N/A N/A
15.0 3.1 7.2 1950 53.7 42.2 5.35 72.0 10.0 9.9
N/A N/A N/A N/A N/A N/A
120
7.5 0.0 0.0 1465 45.0 32.5 6.32 66.6 7.1 12.1
N/A N/A N/A N/A N/A N/A
7.5 0.0 0.0 1950 46.9 39.0 6.53 69.2 7.2 12.6
N/A N/A N/A N/A N/A N/A
11.3 1.7 3.9 1465 46.9 33.3 5.93 67.2 7.9 11.7
N/A N/A N/A N/A N/A N/A
11.3 1.7 3.9 1950 48.9 39.9 6.13 69.9 8.0 12.2
N/A N/A N/A N/A N/A N/A
15.0 2.9 6.7 1465 48.0 33.7 5.74 67.6 8.4 11.3
N/A N/A N/A N/A N/A N/A
15.0 2.9 6.7 1950 50.0 40.4 5.94 70.3 8.4 11.7
N/A N/A N/A N/A N/A N/A
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not re ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Operation not recommended
Operation not recommended