Residential Products Technical Guide
Performance Data — GT-PG Model 030 - PSC Blower
950 CFM Nominal (Rated) Air ow Cooling,950 CFM Nominal (Rated) Air ow Heating Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Air ow
CFM
TC SC kW HR EER HW
Air ow
CFM
HC kW HE LAT COP HW
20
8.0 5.6 12.9
N/A N/A N/A N/A N/A N/A N/A 715 19.9 2.10 13.1 96 2.78 2.0
8.0 5.6 12.9
N/A N/A N/A N/A N/A N/A N/A 950 20.4 1.92 13.9 90 3.12 2.1
30
4.0 1.5 3.5 715 28.8 16.3 1.18 32.8 24.4 0.6 715 21.7 2.13 14.8 98 2.99 2.5
4.0 1.5 3.5 950 30.0 19.5 1.22 34.1 24.6 0.6 950 22.3 1.95 15.7 92 3.36 2.5
6.0 3.1 7.2 715 28.9 16.3 1.14 32.8 25.3 0.5 715 22.5 2.14 15.6 99 3.08 2.6
6.0 3.1 7.2 950 30.1 19.6 1.18 34.1 25.5 0.6 950 23.1 1.96 16.5 93 3.46 2.6
8.0 5.1 11.8 715 29.0 16.4 1.11 32.8 26.0 0.5 715 23.0 2.15 16.0 100 3.13 2.7
8.0 5.1 11.8 950 30.2 19.6 1.15 34.1 26.2 0.5 950 23.6 1.97 16.9 93 3.52 2.7
40
4.0 1.3 3.0 715 31.0 17.8 1.30 35.5 23.9 1.0 715 24.7 2.18 17.5 102 3.32 2.9
4.0 1.3 3.0 950 32.3 21.3 1.34 36.9 24.1 1.0 950 25.3 1.99 18.6 95 3.72 2.9
6.0 2.8 6.5 715 31.2 17.8 1.25 35.5 24.9 0.9 715 25.6 2.20 18.4 103 3.42 3.0
6.0 2.8 6.5 950 32.5 21.3 1.30 36.9 25.1 1.0 950 26.3 2.01 19.5 96 3.84 3.0
8.0 4.5 10.4 715 31.4 17.8 1.22 35.5 25.7 0.8 715 26.2 2.21 18.9 104 3.47 3.1
8.0 4.5 10.4 950 32.7 21.4 1.26 36.9 25.9 0.9 950 26.9 2.02 20.0 96 3.90 3.2
50
4.0 1.3 3.0 715 31.9 18.5 1.44 36.8 22.2 1.6 715 27.7 2.24 20.2 106 3.62 3.3
4.0 1.3 3.0 950 33.2 22.2 1.49 38.3 22.4 1.6 950 28.4 2.05 21.4 98 4.07 3.3
6.0 2.6 6.0 715 32.2 18.5 1.37 36.8 23.4 1.4 715 28.8 2.26 21.2 107 3.74 3.4
6.0 2.6 6.0 950 33.5 22.2 1.42 38.3 23.6 1.5 950 29.6 2.07 22.5 99 4.19 3.5
8.0 4.3 9.9 715 32.3 18.5 1.34 36.9 24.2 1.3 715 29.4 2.27 21.8 108 3.79 3.5
8.0 4.3 9.9 950 33.7 22.2 1.38 38.3 24.4 1.3 950 30.2 2.08 23.1 99 4.26 3.6
60
4.0 1.2 2.8 715 31.0 18.2 1.60 36.4 19.4 2.2 715 30.6 2.30 22.9 110 3.91 3.7
4.0 1.2 2.8 950 32.3 21.8 1.65 37.9 19.6 2.3 950 31.5 2.10 24.3 101 4.39 3.8
6.0 2.5 5.8 715 31.7 18.5 1.51 36.8 21.1 2.0 715 31.9 2.32 24.1 111 4.03 3.8
6.0 2.5 5.8 950 33.0 22.1 1.56 38.3 21.2 2.0 950 32.8 2.12 25.6 102 4.53 3.9
8.0 4.0 9.2 715 32.0 18.5 1.46 36.9 21.9 1.7 715 32.6 2.34 24.7 112 4.09 4.0
8.0 4.0 9.2 950 33.3 22.2 1.51 38.4 22.0 1.8 950 33.5 2.14 26.2 103 4.60 4.1
70
4.0 1.1 2.5 715 29.5 17.6 1.76 35.5 16.8 2.9 715 33.6 2.36 25.6 114 4.18 3.8
4.0 1.1 2.5 950 30.7 21.1 1.81 36.9 16.9 3.0 950 34.5 2.16 27.2 104 4.69 4.0
6.0 2.3 5.3 715 30.5 18.0 1.65 36.1 18.4 2.6 715 35.1 2.39 26.9 115 4.30 4.0
6.0 2.3 5.3 950 31.7 21.6 1.71 37.5 18.5 2.7 950 36.0 2.18 28.5 105 4.83 4.1
8.0 3.8 8.8 715 30.9 18.2 1.61 36.4 19.2 2.3 715 35.8 2.40 27.6 116 4.36 4.2
8.0 3.8 8.8 950 32.2 21.8 1.66 37.8 19.4 2.4 950 36.8 2.20 29.3 106 4.90 4.3
80
4.0 1.0 2.3 715 27.7 16.8 1.94 34.3 14.3 3.5 715 36.6 2.42 28.3 117 4.43 4.2
4.0 1.0 2.3 950 28.8 20.2 2.00 35.6 14.4 3.6 950 37.5 2.21 30.0 107 4.97 4.3
6.0 2.2 5.1 715 28.8 17.3 1.83 35.0 15.8 3.2 715 38.1 2.46 29.6 119 4.55 4.4
6.0 2.2 5.1 950 30.0 20.7 1.89 36.4 15.9 3.4 950 39.1 2.25 31.4 108 5.11 4.5
8.0 3.5 8.1 715 29.3 17.5 1.77 35.4 16.6 3.0 715 38.9 2.47 30.4 120 4.61 4.5
8.0 3.5 8.1 950 30.5 21.0 1.83 36.8 16.7 3.1 950 40.0 2.26 32.2 109 5.18 4.7
85
4.0 1.0 2.3 715 26.7 16.4 2.04 33.7 13.1 3.9 715 38.0 2.45 29.5 119 4.54 4.4
4.0 1.0 2.3 950 27.8 19.7 2.11 35.0 13.2 4.1 950 39.0 2.24 31.4 108 5.10 4.5
6.0 2.2 5.0 715 27.8 16.9 1.92 34.4 14.5 3.6 715 39.6 2.49 31.0 121 4.66 4.6
6.0 2.2 5.0 950 29.0 20.2 1.99 35.8 14.6 3.8 950 40.6 2.28 32.8 110 5.23 4.7
8.0 3.5 8.0 715 28.4 17.1 1.87 34.7 15.2 3.3 715 40.4 2.51 31.7 122 4.72 4.7
8.0 3.5 8.0 950 29.6 20.5 1.93 36.1 15.3 3.5 950 41.5 2.30 33.6 110 5.30 4.9
90
4.0 1.0 2.3 715 25.7 16.0 2.15 33.1 12.0 4.5 715 39.4 2.49 30.8 121 4.65 4.6
4.0 1.0 2.3 950 26.8 19.2 2.22 34.4 12.1 4.6 950 40.5 2.27 32.7 109 5.22 4.7
6.0 2.1 4.9 715 26.9 16.5 2.02 33.8 13.3 4.1 715 41.1 2.53 32.3 123 4.77 4.7
6.0 2.1 4.9 950 28.0 19.7 2.09 35.1 13.4 4.3 950 42.2 2.31 34.3 111 5.35 4.9
8.0 3.4 7.9 715 27.4 16.7 1.96 34.1 14.0 3.8 715 41.9 2.55 33.0 124 4.82 4.9
8.0 3.4 7.9 950 28.6 20.0 2.03 35.5 14.1 4.0 950 43.0 2.33 35.1 112 5.42 5.1
100
4.0 1.0 2.3 715 23.9 15.3 2.39 32.1 10.0 4.9
N/A N/A N/A N/A N/A N/A
4.0 1.0 2.3 950 24.9 18.3 2.47 33.4 10.1 5.1
N/A N/A N/A N/A N/A N/A
6.0 1.9 4.4 715 23.2 15.0 2.51 31.7 9.2 4.7
N/A N/A N/A N/A N/A N/A
6.0 1.9 4.4 950 24.1 17.9 2.60 33.0 9.3 4.9
N/A N/A N/A N/A N/A N/A
8.0 3.1 7.2 715 23.6 15.2 2.44 31.9 9.7 4.5
N/A N/A N/A N/A N/A N/A
8.0 3.1 7.2 950 24.6 18.1 2.52 33.2 9.8 4.7
N/A N/A N/A N/A N/A N/A
110
4.0 0.9 2.1 715 22.4 14.7 2.68 31.5 8.4 5.9
N/A N/A N/A N/A N/A N/A
4.0 0.9 2.1 950 23.3 17.6 2.77 32.8 8.4 6.1
N/A N/A N/A N/A N/A N/A
6.0 1.9 4.4 715 23.2 15.0 2.51 31.7 9.2 5.7
N/A N/A N/A N/A N/A N/A
6.0 1.9 4.4 950 24.1 17.9 2.60 33.0 9.3 5.9
N/A N/A N/A N/A N/A N/A
8.0 3.1 7.2 715 23.6 15.2 2.44 31.9 9.7 5.5
N/A N/A N/A N/A N/A N/A
8.0 3.1 7.2 950 24.6 18.1 2.52 33.2 9.8 5.7
N/A N/A N/A N/A N/A N/A
120
4.0 0.9 2.1 715 21.3 14.6 3.02 31.6 7.1 6.9
N/A N/A N/A N/A N/A N/A
4.0 0.9 2.1 950 22.2 17.4 3.12 32.9 7.1 7.2
N/A N/A N/A N/A N/A N/A
6.0 1.8 4.2 715 21.8 14.6 2.82 31.5 7.7 6.7
N/A N/A N/A N/A N/A N/A
6.0 1.8 4.2 950 22.7 17.5 2.92 32.7 7.8 7.0
N/A N/A N/A N/A N/A N/A
8.0 3.0 6.9 715 22.1 14.7 2.74 31.5 8.1 6.4
N/A N/A N/A N/A N/A N/A
8.0 3.0 6.9 950 23.0 17.6 2.83 32.7 8.1 6.7
N/A N/A N/A N/A N/A N/A
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not re ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Operation not recommended