Bryant GT-PG (50YE) Heating System User Manual


 
GT-PG
16
GT-PG (50YE) Series
Bryant: Whatever it Takes.
Performance Data — GT-PG Model 024 - ECM Blower
850 CFM Nominal (Rated) Air ow Cooling, 950 CFM Nominal (Rated) Air ow Heating Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Air ow
CFM
TC SC kW HR EER HW
Air ow
CFM
HC kW HE LAT COP HW
20
8.0 5.6 12.9
N/A N/A N/A N/A N/A N/A N/A 690 16.0 1.70 10.6 92 2.76 1.7
8.0 5.6 12.9
N/A N/A N/A N/A N/A N/A N/A 950 16.5 1.57 11.2 86 3.08 1.7
30
4.0 1.5 3.5 610 28.1 16.1 0.78 30.6 35.9 0.6 690 18.1 1.73 12.5 94 3.07 2.0
4.0 1.5 3.5 850 29.2 18.7 0.83 31.9 35.3 0.6 950 18.7 1.60 13.3 88 3.43 2.0
6.0 3.1 7.2 610 28.1 16.1 0.76 30.6 37.1 0.5 690 18.8 1.74 13.2 95 3.17 2.1
6.0 3.1 7.2 850 29.3 18.7 0.80 31.9 36.5 0.6 950 19.4 1.61 14.0 89 3.54 2.1
8.0 5.1 11.8 610 28.2 16.1 0.74 30.7 38.1 0.5 690 19.2 1.74 13.5 96 3.23 2.1
8.0 5.1 11.8 850 29.3 18.8 0.78 32.0 37.5 0.5 950 19.8 1.61 14.3 89 3.60 2.2
40
4.0 1.3 3.0 610 28.4 16.6 0.89 31.3 31.9 1.0 690 21.0 1.77 15.2 98 3.48 2.3
4.0 1.3 3.0 850 29.5 19.3 0.94 32.7 31.3 1.0 950 21.7 1.64 16.1 91 3.89 2.3
6.0 2.8 6.5 610 28.6 16.6 0.84 31.4 34.1 0.9 690 21.9 1.78 16.0 99 3.60 2.4
6.0 2.8 6.5 850 29.7 19.3 0.89 32.7 33.5 0.9 950 22.5 1.65 17.0 92 4.01 2.4
8.0 4.5 10.4 610 28.7 16.6 0.82 31.4 35.2 0.8 690 22.3 1.79 16.4 100 3.65 2.5
8.0 4.5 10.4 850 29.9 19.3 0.86 32.8 34.6 0.9 950 23.0 1.65 17.4 92 4.08 2.5
50
4.0 1.3 3.0 610 28.2 16.7 1.00 31.5 28.1 1.5 690 23.9 1.81 17.8 102 3.86 2.6
4.0 1.3 3.0 850 29.3 19.4 1.06 32.9 27.7 1.6 950 24.6 1.67 18.9 94 4.31 2.7
6.0 2.6 6.0 610 28.5 16.8 0.94 31.6 30.4 1.4 690 24.8 1.83 18.7 103 3.99 2.7
6.0 2.6 6.0 850 29.7 19.5 0.99 33.0 29.8 1.5 950 25.6 1.69 19.9 95 4.45 2.8
8.0 4.3 9.9 610 28.6 16.8 0.91 31.7 31.5 1.3 690 25.3 1.83 19.1 104 4.05 2.8
8.0 4.3 9.9 850 29.8 19.5 0.96 33.0 30.9 1.3 950 26.1 1.69 20.3 95 4.52 2.9
60
4.0 1.2 2.8 610 27.3 16.4 1.13 31.1 24.1 2.1 690 26.7 1.85 20.4 106 4.22 2.9
4.0 1.2 2.8 850 28.4 19.1 1.20 32.5 23.7 2.2 950 27.5 1.71 21.7 97 4.71 3.0
6.0 2.5 5.8 610 27.8 16.6 1.06 31.4 26.3 1.9 690 27.7 1.87 21.3 107 4.35 3.0
6.0 2.5 5.8 850 28.9 19.3 1.12 32.7 25.8 2.0 950 28.6 1.73 22.7 98 4.85 3.1
8.0 4.0 9.2 610 28.1 16.7 1.02 31.5 27.4 1.7 690 28.3 1.88 21.8 108 4.41 3.2
8.0 4.0 9.2 850 29.2 19.4 1.08 32.8 26.9 1.8 950 29.1 1.73 23.2 98 4.92 3.2
70
4.0 1.1 2.5 610 26.1 16.0 1.28 30.5 20.4 2.8 690 29.4 1.89 22.8 109 4.54 3.3
4.0 1.1 2.5 850 27.2 18.7 1.36 31.8 20.0 3.0 950 30.3 1.75 24.3 99 5.07 3.4
6.0 2.3 5.3 610 26.8 16.3 1.20 30.8 22.3 2.5 690 30.5 1.91 23.9 111 4.67 3.4
6.0 2.3 5.3 850 27.9 18.9 1.27 32.2 22.0 2.6 950 31.4 1.77 25.4 101 5.21 3.5
8.0 3.8 8.8 610 27.1 16.4 1.16 31.0 23.4 2.3 690 31.1 1.92 24.4 112 4.74 3.5
8.0 3.8 8.8 850 28.2 19.1 1.23 32.3 23.0 2.3 950 32.0 1.77 25.9 101 5.29 3.6
80
4.0 1.0 2.3 610 24.8 15.6 1.45 29.7 17.1 3.4 690 31.9 1.93 25.2 113 4.84 3.6
4.0 1.0 2.3 850 25.8 18.1 1.54 31.0 16.8 3.5 950 32.9 1.79 26.8 102 5.40 3.7
6.0 2.2 5.1 610 25.5 15.8 1.36 30.1 18.7 3.1 690 33.1 1.95 26.3 114 4.97 3.7
6.0 2.2 5.1 850 26.5 18.4 1.44 31.4 18.4 3.3 950 34.1 1.80 27.9 103 5.54 3.8
8.0 3.5 8.1 610 25.9 15.9 1.32 30.3 19.6 2.9 690 33.7 1.96 26.9 115 5.04 3.8
8.0 3.5 8.1 850 26.9 18.6 1.39 31.6 19.3 3.0 950 34.8 1.81 28.5 104 5.62 3.9
85
4.0 1.0 2.3 610 24.0 15.3 1.55 29.3 15.5 3.8 690 33.2 1.95 26.3 114 4.98 3.7
4.0 1.0 2.3 850 25.0 17.8 1.64 30.6 15.2 3.9 950 34.2 1.80 28.0 103 5.55 3.8
6.0 2.2 5.0 610 24.8 15.6 1.45 29.7 17.0 3.5 690 34.3 1.97 27.4 116 5.10 3.9
6.0 2.2 5.0 850 25.8 18.1 1.54 31.0 16.8 3.7 950 35.4 1.82 29.2 105 5.69 4.0
8.0 3.5 8.0 610 25.1 15.7 1.41 29.9 17.9 3.2 690 35.0 1.98 28.0 117 5.17 4.0
8.0 3.5 8.0 850 26.1 18.3 1.49 31.2 17.6 3.4 950 36.0 1.83 29.8 105 5.77 4.1
90
4.0 1.0 2.3 610 23.3 15.0 1.65 28.9 14.1 4.3 690 34.4 1.97 27.5 116 5.11 3.9
4.0 1.0 2.3 850 24.2 17.5 1.74 30.2 13.9 4.5 950 35.5 1.82 29.2 105 5.70 4.0
6.0 2.1 4.9 610 24.0 15.3 1.55 29.3 15.6 4.0 690 35.6 1.99 28.6 118 5.23 4.0
6.0 2.1 4.9 850 25.0 17.8 1.63 30.6 15.3 4.2 950 36.7 1.84 30.4 106 5.84 4.1
8.0 3.4 7.9 610 24.4 15.4 1.50 29.5 16.3 3.7 690 36.2 2.00 29.1 119 5.30 4.2
8.0 3.4 7.9 850 25.4 18.0 1.58 30.8 16.0 3.8 950 37.3 1.85 31.0 106 5.91 4.3
100
4.0 1.0 2.3 610 21.8 14.5 1.86 28.2 11.7 4.7
N/A N/A N/A N/A N/A N/A
4.0 1.0 2.3 850 22.6 16.9 1.97 29.4 11.5 4.9
N/A N/A N/A N/A N/A N/A
6.0 2.0 4.6 610 22.5 14.8 1.75 28.5 12.8 4.6
N/A N/A N/A N/A N/A N/A
6.0 2.0 4.6 850 23.4 17.2 1.86 29.7 12.6 4.7
N/A N/A N/A N/A N/A N/A
8.0 3.2 7.4 610 22.9 14.9 1.70 28.7 13.5 4.4
N/A N/A N/A N/A N/A N/A
8.0 3.2 7.4 850 23.8 17.3 1.80 29.9 13.2 4.6
N/A N/A N/A N/A N/A N/A
110
4.0 0.9 2.1 610 20.3 14.1 2.11 27.5 9.6 5.7
N/A N/A N/A N/A N/A N/A
4.0 0.9 2.1 850 21.1 16.4 2.23 28.7 9.4 5.9
N/A N/A N/A N/A N/A N/A
6.0 1.9 4.4 610 21.0 14.3 1.99 27.8 10.5 5.5
N/A N/A N/A N/A N/A N/A
6.0 1.9 4.4 850 21.8 16.6 2.10 29.0 10.4 5.7
N/A N/A N/A N/A N/A N/A
8.0 3.1 7.2 610 21.3 14.4 1.93 28.0 11.1 5.3
N/A N/A N/A N/A N/A N/A
8.0 3.1 7.2 850 22.2 16.7 2.04 29.2 10.9 5.5
N/A N/A N/A N/A N/A N/A
120
4.0 0.9 2.1 610 18.9 13.7 2.39 27.1 7.9 6.7
N/A N/A N/A N/A N/A N/A
4.0 0.9 2.1 850 19.7 16.0 2.52 28.3 7.8 7.0
N/A N/A N/A N/A N/A N/A
6.0 1.8 4.2 610 19.5 13.9 2.25 27.3 8.7 6.5
N/A N/A N/A N/A N/A N/A
6.0 1.8 4.2 850 20.3 16.2 2.38 28.5 8.5 6.7
N/A N/A N/A N/A N/A N/A
8.0 3.0 6.9 610 19.9 14.0 2.19 27.4 9.1 6.2
N/A N/A N/A N/A N/A N/A
8.0 3.0 6.9 850 20.6 16.3 2.31 28.6 8.9 6.5
N/A N/A N/A N/A N/A N/A
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not re ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Operation not recommended
Operation not recommended