Bryant GT-PG (50YE) Heating System User Manual


 
Bryant Geothermal Heat Pump Systems
GT-PG
15
Residential Products Technical Guide
Performance Data — GT-PG Model 024 - PSC Blower
850 CFM Nominal (Rated) Air ow Cooling, 850 CFM Nominal (Rated) Air ow Heating Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Air ow
CFM
TC SC kW HR EER HW
Air ow
CFM
HC kW HE LAT COP HW
20
8.0 5.6 12.9
N/A N/A N/A N/A N/A N/A N/A 640 16.3 1.80 10.6 94 2.66 1.6
8.0 5.6 12.9
N/A N/A N/A N/A N/A N/A N/A 850 16.8 1.65 11.2 88 2.99 1.7
30
4.0 1.5 3.5 640 27.9 15.6 0.94 31.1 29.8 0.6 640 18.5 1.83 12.5 97 2.95 2.0
4.0 1.5 3.5 850 29.1 18.7 0.97 32.4 30.0 0.6 850 19.0 1.68 13.3 91 3.32 2.0
6.0 3.1 7.2 640 28.0 15.6 0.90 31.1 31.1 0.5 640 19.2 1.84 13.2 98 3.05 2.0
6.0 3.1 7.2 850 29.2 18.7 0.93 32.4 31.3 0.6 850 19.7 1.68 14.0 91 3.42 2.1
8.0 5.1 11.8 640 28.1 15.7 0.88 31.1 31.8 0.5 640 19.5 1.85 13.5 98 3.10 2.1
8.0 5.1 11.8 850 29.3 18.8 0.91 32.4 32.1 0.5 850 20.0 1.69 14.3 92 3.48 2.2
40
4.0 1.3 3.0 640 27.8 15.8 1.04 31.3 26.9 1.0 640 21.4 1.87 15.2 101 3.34 2.3
4.0 1.3 3.0 850 29.0 18.9 1.07 32.6 27.1 1.0 850 22.0 1.71 16.1 94 3.75 2.3
6.0 2.8 6.5 640 28.0 15.8 0.99 31.4 28.5 0.9 640 22.2 1.89 16.0 102 3.45 2.3
6.0 2.8 6.5 850 29.2 18.9 1.02 32.6 28.7 0.9 850 22.8 1.72 17.0 95 3.87 2.4
8.0 4.5 10.4 640 28.2 15.8 0.96 31.4 29.3 0.8 640 22.6 1.89 16.4 103 3.51 2.4
8.0 4.5 10.4 850 29.3 18.9 0.99 32.7 29.5 0.9 850 23.3 1.73 17.4 95 3.94 2.5
50
4.0 1.3 3.0 640 27.6 15.9 1.15 31.5 24.1 1.5 640 24.2 1.92 17.8 105 3.71 2.6
4.0 1.3 3.0 850 28.7 19.0 1.18 32.7 24.3 1.6 850 24.9 1.75 18.9 97 4.16 2.6
6.0 2.6 6.0 640 27.8 15.9 1.08 31.5 25.7 1.4 640 25.2 1.93 18.7 106 3.82 2.7
6.0 2.6 6.0 850 29.0 19.1 1.12 32.8 25.9 1.5 850 25.9 1.76 19.9 98 4.29 2.7
8.0 4.3 9.9 640 27.9 15.9 1.06 31.5 26.5 1.3 640 25.7 1.94 19.2 107 3.89 2.8
8.0 4.3 9.9 850 29.1 19.1 1.09 32.8 26.7 1.3 850 26.4 1.77 20.3 99 4.36 2.8
60
4.0 1.2 2.8 640 26.9 15.9 1.27 31.2 21.1 2.1 640 27.0 1.96 20.4 109 4.05 2.9
4.0 1.2 2.8 850 28.0 19.1 1.32 32.5 21.3 2.2 850 27.7 1.79 21.7 100 4.54 3.0
6.0 2.5 5.8 640 27.3 15.9 1.20 31.4 22.7 1.9 640 28.1 1.97 21.4 111 4.17 3.0
6.0 2.5 5.8 850 28.4 19.1 1.24 32.6 22.9 2.0 850 28.8 1.80 22.7 101 4.68 3.1
8.0 4.0 9.2 640 27.5 15.9 1.17 31.4 23.5 1.7 640 28.6 1.98 21.9 111 4.23 3.1
8.0 4.0 9.2 850 28.6 19.1 1.21 32.7 23.7 1.8 850 29.4 1.81 23.2 102 4.75 3.2
70
4.0 1.1 2.5 640 26.0 15.8 1.42 30.8 18.2 2.8 640 29.7 2.00 22.9 113 4.36 3.2
4.0 1.1 2.5 850 27.0 18.9 1.47 32.0 18.4 3.0 850 30.5 1.83 24.3 103 4.89 3.3
6.0 2.3 5.3 640 26.5 15.9 1.34 31.1 19.8 2.5 640 30.8 2.02 23.9 115 4.48 3.3
6.0 2.3 5.3 850 27.6 19.0 1.39 32.3 19.9 2.6 850 31.7 1.84 25.4 104 5.04 3.4
8.0 3.8 8.8 640 26.7 15.9 1.30 31.2 20.5 2.3 640 31.4 2.02 24.5 115 4.55 3.5
8.0 3.8 8.8 850 27.8 19.0 1.35 32.4 20.7 2.3 850 32.3 1.85 25.9 105 5.11 3.6
80
4.0 1.0 2.3 640 24.8 15.6 1.59 30.2 15.6 3.4 640 32.3 2.04 25.3 117 4.65 3.5
4.0 1.0 2.3 850 25.8 18.6 1.65 31.5 15.7 3.5 850 33.2 1.86 26.8 106 5.22 3.6
6.0 2.2 5.1 640 25.4 15.7 1.50 30.6 16.9 3.1 640 33.5 2.06 26.3 118 4.77 3.6
6.0 2.2 5.1 850 26.5 18.8 1.55 31.8 17.1 3.3 850 34.4 1.88 27.9 107 5.36 3.7
8.0 3.5 8.1 640 25.7 15.8 1.46 30.7 17.7 2.9 640 34.1 2.07 26.9 119 4.83 3.8
8.0 3.5 8.1 850 26.8 18.9 1.51 31.9 17.8 3.0 850 35.0 1.89 28.5 108 5.43 3.9
85
4.0 1.0 2.3 640 24.1 15.4 1.69 29.9 14.3 3.8 640 33.5 2.06 26.4 119 4.78 3.7
4.0 1.0 2.3 850 25.1 18.4 1.75 31.1 14.4 3.9 850 34.4 1.88 28.0 108 5.36 3.8
6.0 2.2 5.0 640 24.8 15.5 1.59 30.2 15.6 3.5 640 34.7 2.08 27.5 120 4.90 3.8
6.0 2.2 5.0 850 25.8 18.6 1.65 31.5 15.7 3.7 850 35.7 1.90 29.2 109 5.50 3.9
8.0 3.5 8.0 640 25.1 15.6 1.55 30.4 16.2 3.2 640 35.4 2.09 28.0 121 4.96 3.9
8.0 3.5 8.0 850 26.2 18.7 1.60 31.6 16.4 3.4 850 36.3 1.91 29.8 110 5.57 4.1
90
4.0 1.0 2.3 640 23.5 15.2 1.79 29.6 13.1 4.3 640 34.8 2.08 27.5 120 4.90 3.8
4.0 1.0 2.3 850 24.4 18.2 1.85 30.8 13.2 4.5 850 35.7 1.90 29.2 109 5.51 3.9
6.0 2.1 4.9 640 24.2 15.4 1.69 29.9 14.3 4.0 640 36.0 2.10 28.6 122 5.03 4.0
6.0 2.1 4.9 850 25.2 18.4 1.74 31.1 14.4 4.2 850 37.0 1.92 30.4 110 5.64 4.1
8.0 3.4 7.9 640 24.5 15.5 1.64 30.1 15.0 3.7 640 36.6 2.11 29.2 123 5.09 4.1
8.0 3.4 7.9 850 25.5 18.5 1.69 31.3 15.1 3.8 850 37.6 1.93 31.0 111 5.71 4.2
100
4.0 1.0 2.3 640 21.9 14.7 2.02 28.8 10.9 4.7
N/A N/A N/A N/A N/A N/A
4.0 1.0 2.3 850 22.8 17.6 2.08 30.0 11.0 4.9
N/A N/A N/A N/A N/A N/A
6.0 2.0 4.6 640 22.7 14.9 1.90 29.2 12.0 4.6
N/A N/A N/A N/A N/A N/A
6.0 2.0 4.6 850 23.7 17.9 1.96 30.4 12.0 4.7
N/A N/A N/A N/A N/A N/A
8.0 3.2 7.4 640 23.1 15.1 1.84 29.4 12.5 4.4
N/A N/A N/A N/A N/A N/A
8.0 3.2 7.4 850 24.1 18.1 1.91 30.6 12.6 4.6
N/A N/A N/A N/A N/A N/A
110
4.0 0.9 2.1 640 20.2 14.0 2.27 28.0 8.9 5.7
N/A N/A N/A N/A N/A N/A
4.0 0.9 2.1 850 21.1 16.8 2.34 29.1 9.0 5.9
N/A N/A N/A N/A N/A N/A
6.0 1.9 4.4 640 21.1 14.4 2.14 28.4 9.8 5.5
N/A N/A N/A N/A N/A N/A
6.0 1.9 4.4 850 22.0 17.2 2.21 29.5 9.9 5.7
N/A N/A N/A N/A N/A N/A
8.0 3.1 7.2 640 21.5 14.5 2.08 28.6 10.3 5.3
N/A N/A N/A N/A N/A N/A
8.0 3.1 7.2 850 22.4 17.4 2.15 29.7 10.4 5.5
N/A N/A N/A N/A N/A N/A
120
4.0 0.9 2.1 640 18.4 13.2 2.55 27.1 7.2 6.7
N/A N/A N/A N/A N/A N/A
4.0 0.9 2.1 850 19.2 15.8 2.64 28.2 7.3 7.0
N/A N/A N/A N/A N/A N/A
6.0 1.8 4.2 640 19.3 13.6 2.41 27.5 8.0 6.5
N/A N/A N/A N/A N/A N/A
6.0 1.8 4.2 850 20.1 16.3 2.49 28.6 8.1 6.7
N/A N/A N/A N/A N/A N/A
8.0 3.0 6.9 640 19.7 13.8 2.35 27.8 8.4 6.2
N/A N/A N/A N/A N/A N/A
8.0 3.0 6.9 850 20.6 16.5 2.42 28.9 8.5 6.5
N/A N/A N/A N/A N/A N/A
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not re ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Operation not recommended
Operation not recommended