Bryant GT-PG (50YE) Heating System User Manual


 
GT-PG
20
GT-PG (50YE) Series
Bryant: Whatever it Takes.
Performance Data — GT-PG Model 036 - ECM Blower
1,250 CFM Nominal (Rated) Air ow Cooling, 1,250 CFM Nominal (Rated) Air ow Heating Performance capacities shown in thousands of Btuh
EWT
°F
GPM
WPD Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT
Air ow
CFM
TC SC kW HR EER HW
Air ow
CFM
HC kW HE LAT COP HW
20
9.0 5.9 13.6
N/A N/A N/A N/A N/A N/A N/A 900 21.5 2.06 14.8 92 3.06 2.1
9.0 5.9 13.6
N/A N/A N/A N/A N/A N/A N/A 1250 22.1 1.90 15.7 86 3.42 2.2
30
4.5 1.7 3.9 900 33.0 19.5 1.16 36.9 28.5 0.6 900 23.7 2.09 16.9 94 3.33 2.5
4.5 1.7 3.9 1250 34.3 22.7 1.22 38.4 28.0 0.6 1250 24.5 1.93 17.9 88 3.72 2.6
6.8 3.3 7.6 900 33.1 19.5 1.13 36.9 29.4 0.6 900 24.7 2.10 17.8 95 3.45 2.6
6.8 3.3 7.6 1250 34.4 22.7 1.19 38.4 28.9 0.6 1250 25.5 1.94 18.9 89 3.84 2.7
9.0 5.7 13.2 900 33.3 19.6 1.10 36.9 30.3 0.5 900 25.3 2.11 18.3 96 3.51 2.7
9.0 5.7 13.2 1250 34.6 22.8 1.16 38.5 29.8 0.6 1250 26.1 1.95 19.4 89 3.91 2.8
40
4.5 1.5 3.5 900 36.1 22.4 1.29 40.4 28.1 1.1 900 27.3 2.14 20.1 98 3.73 2.9
4.5 1.5 3.5 1250 37.5 26.1 1.36 42.2 27.6 1.1 1250 28.1 1.98 21.4 91 4.17 3.0
6.8 3.2 7.4 900 36.3 22.4 1.24 40.5 29.2 1.0 900 28.5 2.16 21.3 99 3.87 3.0
6.8 3.2 7.4 1250 37.7 26.1 1.32 42.2 28.7 1.0 1250 29.4 2.00 22.6 92 4.32 3.1
9.0 5.4 12.5 900 36.7 22.5 1.21 40.7 30.3 0.9 900 29.2 2.17 21.9 100 3.94 3.2
9.0 5.4 12.5 1250 38.1 26.2 1.28 42.4 29.8 0.9 1250 30.1 2.01 23.3 92 4.40 3.2
50
4.5 1.3 3.0 900 37.1 23.9 1.42 41.9 26.1 1.8 900 30.9 2.20 23.5 102 4.12 3.4
4.5 1.3 3.0 1250 38.6 27.9 1.51 43.7 25.6 1.8 1250 31.9 2.03 25.0 94 4.60 3.4
6.8 3.1 7.2 900 37.4 23.8 1.37 42.0 27.3 1.6 900 32.4 2.22 24.8 103 4.27 3.5
6.8 3.1 7.2 1250 38.9 27.7 1.45 43.8 26.9 1.7 1250 33.4 2.05 26.4 95 4.77 3.6
9.0 5.2 12.0 900 37.6 23.8 1.33 42.1 28.3 1.4 900 33.2 2.23 25.6 104 4.35 3.6
9.0 5.2 12.0 1250 39.1 27.6 1.41 43.9 27.8 1.5 1250 34.2 2.06 27.2 95 4.85 3.7
60
4.5 1.2 2.8 900 36.3 23.8 1.60 41.7 22.7 2.4 900 34.6 2.26 26.9 106 4.49 3.8
4.5 1.2 2.8 1250 37.8 27.7 1.69 43.5 22.4 2.5 1250 35.7 2.09 28.6 96 5.01 3.9
6.8 2.9 6.7 900 37.1 24.1 1.50 42.1 24.7 2.2 900 36.3 2.29 28.4 107 4.65 3.9
6.8 2.9 6.7 1250 38.5 28.0 1.59 43.9 24.2 2.3 1250 37.4 2.11 30.2 98 5.19 4.0
9.0 5.0 11.6 900 37.3 24.1 1.46 42.2 25.6 1.9 900 37.2 2.30 29.3 108 4.74 4.1
9.0 5.0 11.6 1250 38.8 28.0 1.54 44.0 25.1 2.0 1250 38.4 2.13 31.1 98 5.29 4.2
70
4.5 1.1 2.5 900 34.6 23.1 1.76 40.6 19.7 3.3 900 38.3 2.32 30.3 109 4.84 4.2
4.5 1.1 2.5 1250 36.0 26.9 1.86 42.3 19.4 3.4 1250 39.5 2.15 32.2 99 5.40 4.4
6.8 2.9 6.7 900 35.8 23.6 1.65 41.4 21.6 2.9 900 40.2 2.35 32.0 111 5.01 4.4
6.8 2.9 6.7 1250 37.2 27.5 1.75 43.1 21.3 3.1 1250 41.5 2.18 34.0 101 5.58 4.5
9.0 4.8 11.1 900 36.3 23.8 1.60 41.7 22.6 2.6 900 41.2 2.37 32.9 112 5.09 4.6
9.0 4.8 11.1 1250 37.7 27.7 1.70 43.5 22.2 2.7 1250 42.5 2.19 35.0 101 5.68 4.7
80
4.5 1.0 2.3 900 32.5 22.1 1.94 39.1 16.8 3.9 900 42.0 2.39 33.6 113 5.16 4.6
4.5 1.0 2.3 1250 33.8 25.7 2.05 40.8 16.5 4.1 1250 43.3 2.21 35.8 102 5.75 4.8
6.8 2.8 6.5 900 33.9 22.7 1.82 40.0 18.6 3.6 900 44.1 2.43 35.5 115 5.33 4.8
6.8 2.8 6.5 1250 35.2 26.4 1.93 41.8 18.2 3.8 1250 45.5 2.24 37.8 104 5.94 4.9
9.0 4.5 10.4 900 34.5 23.0 1.77 40.5 19.5 3.3 900 45.2 2.45 36.5 117 5.41 5.0
9.0 4.5 10.4 1250 35.9 26.8 1.87 42.2 19.2 3.5 1250 46.6 2.26 38.8 105 6.04 5.1
85
4.5 1.0 2.2 900 31.4 21.5 2.04 38.4 15.4 4.4 900 43.9 2.42 35.3 115 5.30 4.8
4.5 1.0 2.2 1250 32.7 25.1 2.16 40.0 15.1 4.6 1250 45.2 2.24 37.5 103 5.92 5.0
6.8 2.7 6.2 900 32.7 22.2 1.92 39.3 17.0 4.1 900 46.0 2.47 37.3 117 5.47 5.0
6.8 2.7 6.2 1250 34.0 25.8 2.03 41.0 16.7 4.2 1250 47.4 2.28 39.6 105 6.10 5.2
9.0 4.5 10.3 900 33.4 22.5 1.86 39.7 17.9 3.8 900 47.2 2.49 38.3 119 5.55 5.2
9.0 4.5 10.3 1250 34.7 26.2 1.97 41.4 17.6 3.9 1250 48.6 2.30 40.7 106 6.20 5.4
90
4.5 0.9 2.1 900 30.3 21.0 2.14 37.6 14.1 5.0 900 45.7 2.46 37.0 117 5.45 5.0
4.5 0.9 2.1 1250 31.5 24.4 2.27 39.2 13.9 5.2 1250 47.1 2.27 39.3 105 6.08 5.2
6.8 2.6 6.0 900 31.6 21.6 2.02 38.5 15.7 4.7 900 47.9 2.50 39.0 119 5.61 5.2
6.8 2.6 6.0 1250 32.9 25.2 2.14 40.2 15.4 4.8 1250 49.4 2.31 41.4 107 6.26 5.4
9.0 4.4 10.2 900 32.3 22.0 1.96 39.0 16.5 4.3 900 49.1 2.53 40.1 121 5.69 5.4
9.0 4.4 10.2 1250 33.6 25.5 2.07 40.7 16.2 4.5 1250 50.6 2.34 42.6 108 6.35 5.6
100
4.5 0.8 1.8 900 28.2 20.1 2.38 36.3 11.8 5.5
N/A N/A N/A N/A N/A N/A
4.5 0.8 1.8 1250 29.3 23.4 2.52 37.9 11.6 5.7
N/A N/A N/A N/A N/A N/A
6.8 2.6 6.0 900 29.3 20.6 2.24 37.0 13.1 5.3
N/A N/A N/A N/A N/A N/A
6.8 2.6 6.0 1250 30.5 23.9 2.37 38.6 12.9 5.5
N/A N/A N/A N/A N/A N/A
9.0 4.2 9.7 900 30.0 20.9 2.18 37.4 13.8 5.1
N/A N/A N/A N/A N/A N/A
9.0 4.2 9.7 1250 31.2 24.3 2.30 39.0 13.5 5.3
N/A N/A N/A N/A N/A N/A
110
4.5 0.8 1.8 900 26.4 19.6 2.66 35.5 9.9 6.6
N/A N/A N/A N/A N/A N/A
4.5 0.8 1.8 1250 27.4 22.8 2.82 37.1 9.7 6.9
N/A N/A N/A N/A N/A N/A
6.8 2.5 5.8 900 27.3 19.8 2.50 35.9 10.9 6.4
N/A N/A N/A N/A N/A N/A
6.8 2.5 5.8 1250 28.4 23.0 2.65 37.4 10.7 6.6
N/A N/A N/A N/A N/A N/A
9.0 4.0 9.2 900 27.8 20.0 2.43 36.1 11.5 6.2
N/A N/A N/A N/A N/A N/A
9.0 4.0 9.2 1250 28.9 23.2 2.57 37.7 11.3 6.4
N/A N/A N/A N/A N/A N/A
120
4.5 0.7 1.6 900 25.1 19.3 2.98 35.3 8.4 7.8
N/A N/A N/A N/A N/A N/A
4.5 0.7 1.6 1250 26.1 22.5 3.15 36.8 8.3 8.2
N/A N/A N/A N/A N/A N/A
6.8 2.5 5.8 900 25.8 19.5 2.81 35.4 9.2 7.6
N/A N/A N/A N/A N/A N/A
6.8 2.5 5.8 1250 26.8 22.7 2.97 36.9 9.0 7.9
N/A N/A N/A N/A N/A N/A
9.0 3.8 8.8 900 26.1 19.5 2.72 35.5 9.6 7.3
N/A N/A N/A N/A N/A N/A
9.0 3.8 8.8 1250 27.1 22.7 2.88 37.0 9.4 7.6
N/A N/A N/A N/A N/A N/A
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not re ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
For operation in the shaded areas, please see the Performance Data Selection Notes.
Operation not recommended
Operation not recommended