III. STEP 3 — LOCATING AND MOUNTING THE ROOM
CONTROLLER
A. Locating the Room Controller
See Fig. 14 for room controller dimensions. If the air sensor
in the room controller is going to be used, the room controller
should be located by considering the following:
Position controller with a minimum clearance of 5 ft from
the floor.
Locate the unit in the same area as the fan coil unit; pref-
erably on an inside partitioning wall.
Locate on a section of the wall without pipes or ductwork.
Do not locate close to a window, on an outside wall, or
next to a door leading to the outside.
Do not locate where the controller is exposed to direct
light and heat from a lamp, sun, fireplace, or other tem-
perature-radiating object that may cause a false reading.
Do not locate close to, or in direct airflow of, a heating or
cooling supply.
Do not locate in areas with poor circulation, such as
behind a door or in an alcove.
NOTE: Do not exceed 500 ft of network wiring when mount-
ing the room controller.
WARNING: Electrical shock can cause personal
injury and death. Shut off all power to this equipment
during installation. There may be more than one dis-
connect switch. Tag all disconnect locations to alert
others not to restore power until work is completed.
Frame support brackets
Power connection
cables from frame
Power connection
cables from unit
Safety cord
Cable clamp
Frame support
screws
7-7/8”(200 mm)
2%
2” (50 mm)
m
a
x.
Fig. 10 — Condensate Drain Pipe
Fig. 11 — Attach Frame Assembly
Fig. 12 — Fix Frame in Position
A AIR B
A. Gasket "A"
B. Gasket "B"
Fig. 13 — Gasket Location