Table 10 — Evaporator-Fan Motor Performance
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
2. High-static motor not available on size 150 and 151 units.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance data in
Tables 10 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
UNIT
580F
EVAPORATOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
090,091
Standard,
Alternate
208/230
2.40 2120
6.7
460 3.0
575 3.0
High Static
208/230
3.70 3313
12.2
460 5.5
575 5.5
102,103
Standard
208/230
2.40 2120
6.7
460 3.0
575 3.0
High Static
208/230
3.70 3313
12.2
460 5.5
575 5.5
120,121
Standard
208/230
2.40 2120
6.7
460 3.0
575 3.0
Alternate
208/230
2.90 2615
8.6
460 3.9
575 3.9
High Static
208/230
5.25 4400
17.3
460 8.5
575 8.5
150,151
Standard
208/230
3.70 3313
12.2
460 5.5
575 5.5
Alternate
208/230
5.25 4400
17.3
460 8.5
575 8.5