Bryant 580F Heating System User Manual


 
28
Table 8 Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown.
†Indicates standard motor and drive package.
**Indicates alternate motor and drive package.
††Indicates high-static motor and drive package.
Table 9 — Evaporator-Fan Motor Efficiency
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
UNIT 580F
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
6
090,091† 840 815 790 765 740 715 690 665 635 615 590
090,091** 935 910 885 860 835 810 785 760 735 710 685
090,091†† 1080 1025 1007 988 970 952 933 915 897 878 860
102,103† 935 910 885 860 835 810 785 760 735 710 685
102,103†† 1080 1025 1007 988 970 952 933 915 897 878 860
120,121† 935 910 885 860 835 810 785 760 735 710 685
120,121** 1085 1060 1035 1010 985 960 935 910 885 860 835
120,121†† 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
150,151† 1080 1060 1035 1015 990 970 950 925 905 880 860
150,151** 1130 1112 1087 1062 1037 1012 987 962 937 912 887 862 830
UNIT
580F
MOTOR EFFICIENCY
(%)
090-121 80
150,151 87
Fig. 34 — Typical Belt-Drive Motor Mounting
for Sizes 120-151
Fig. 35 — Evaporator-Fan Pulley Adjustment