Table 21 — Air Quantity Limits
Table 22 — Accessory/FIOP Static Pressure (in. wg) — 580F180-300
LEGEND NOTES: The static pressure must be added to external static pressure.
The sum and the evaporator entering-air cfm should then be used in
conjunction with the Fan Performance table to determine blower rpm,
bhp, and watts.
Table 23 — Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown
†Indicates standard drive package.
**Indicates alternate drive package.
††Due to belt and pulley size, pulley cannot be set to this number of turns open.
Table 24 — Evaporator-Fan Motor Data
LEGEND
*Extensive motor and electrical testing on these units ensures that the
full horsepower (brake kilowatt) range of the motors can be utilized
with confidence. Using your fan motors up to the horsepower (brake
kilowatt) ratings shown in this table will not result in nuisance tripping
or premature motor failure. Unit warranty will not be affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
Table 25 — Evaporator-Fan Motor Efficiency
NOTE: All indoor-fan motors 5 hp and larger meet the mini-
mum efficiency requirements as established by the Energy
Policy Act of 1992 (EPACT) effective October 24, 1997.
UNIT
580F
MINIMUM
COOLING CFM
MINIMUM HEATING CFM
MAXIMUM
CFM
Low Heat High Heat
180 4500 3800 3800 7,500
210 5400 4750 5450 9,000
240 6000 4750 5450 10,000
300 7000 4750 5450 11,250
COMPONENT
CFM
4500 5000 5400 6000 7200 7500 9000 10,000 11,250
EconoMi$erIV 0.040 0.050 0.060 0.070 0.090 0.100 0.110 0.120 0.140
Perfect Humidity™ Dehumidification 0.045 0.048 0.060 0.071 0.103 0.111 0.160 0.197 0.250
FIOP Factory-Installed Option
UNIT 580F
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
6
180† †† †† †† †† 1021 1002 984 965 947 928 910 891 873
180** †† †† †† †† 1200 1178 1156 1134 1112 1091 1069 1047 1025
210† †† †† 1095 1077 1058 1040 1021 1002 984 965 947 928 910
210** †† †† 1287 1265 1243 1222 1200 1178 1156 1134 1112 1091 1069
240† †† †† †† †† 1151 1132 1114 1095 1077 1058 1040 1021 1002
240** †† †† †† †† 1369 1347 1325 1303 1281 1259 1237 1215 1193
300† †† †† 1283 1269 1247 1225 1203 1182 1160 1138 1116 1095 1066
300** †† †† †† †† 1551 1524 1497 1470 1443 1415 1388 1361 1332
UNIT
580F
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP
MAXIMUM ACCEPTABLE
CONTINUOUS BkW*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
180
208/230
6.13 4.57 5,180
15.8
460 7.9
210
208/230
5.90 4.40 5,180
15.8
460 7.9
240
208/230 8.70 6.59 7,915 22.0
460 9.50 7.08 8,640 13.0
300
208/230 10.20 7.61 9,510 28.0
460 11.80 8.80 11,000 14.6
BHP Brake Horsepower
BkW Brake Kilowatts
UNIT 580F MOTOR EFFICIENCY (%)
5 Hp 87.5
7.5 Hp 88.5
10 Hp 89.5