Bryant 558F Air Conditioner User Manual


 
84
PERFORMANCE DATA (CONT)
COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY OPTION (cont)
Do not operate at these conditions.
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
where h
ewb
= enthalpy of air entering indoor coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC
.
Correction Factor = 1.10 x (1 BF) x (db 80)
551B120 (10 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
3000/0.025 3200/0.03 4000/0.035 5000/0.04
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
146.2 134.3 122.5 111.4 147.2 135.8 124.3 113.0 147.6 138.4 129.5 123.5 153.6 143.3 136.5 130.2
SHC
42.7 60.0 76.1 93.7 43.5 61.3 79.1 97.4 47.5 68.0 89.5 109.4 49.2 75.2 100.9 123.3
kW
7.09 7.03 6.84 6.72 7.25 7.01 6.89 6.77 7.42 7.10 6.92 6.77 7.79 7.15 7.03 6.88
85
TC
139.5 127.6 115.4 104.6 140.5 128.9 118.1 107.0 132.5 121.5 116.6 137.2 128.0 122.9
SHC
35.4 51.5 68.8 87.2 36.5 53.9 72.0 91.2 61.0 82.7 102.4 68.6 93.6 115.9
kW
8.03 7.96 7.86 7.59 8.20 7.94 7.78 7.51 8.02 7.84 7.69 8.02 7.94 7.79
95
TC
133.5 120.9 108.3 97.8 121.9 111.8 101.0 126.5 113.4 109.7 131.1 119.4 115.5
SHC
29.5 43.0 61.5 80.6 46.5 64.8 84.9 53.9 75.9 95.4 62.0 86.2 108.4
kW
8.97 8.88 8.87 8.46 8.86 8.66 8.26 8.94 8.76 8.60 8.89 8.85 8.69
105
TC
112.0 99.9 90.4 113.1 103.2 93.4 117.2 105.0 100.7 122.1 110.5 105.9
SHC
36.1 54.1 73.8 38.8 57.8 78.9 45.6 68.2 86.8 53.0 78.3 99.7
kW
10.04 9.96 9.62 10.03 9.82 9.48 10.12 9.93 9.82 10.10 10.00 9.90
115
TC
103.0 91.5 83.1 104.3 94.6 85.9 107.8 96.7 91.7 113.0 101.6 96.4
SHC
29.2 46.7 66.9 31.2 50.7 72.9 37.3 60.6 78.3 44.0 70.3 90.9
kW
11.19 11.06 10.78 11.21 10.97 10.70 11.30 11.10 11.03 11.30 11.20 11.10
125
TC
94.1 83.1 75.7 95.5 86.0 78.3 98.5 88.3 82.7 104.0 92.7 86.8
SHC
22.3 39.3 60.1 23.5 43.7 66.8 29.0 52,8 69.7 35.0 62.4 82.2
kW
12.35 12.15 11.94 12.38 12.13 11.92 12.48 12.27 12.25 12.53 12.30 12.28
551B150 (12
1
/
2
TONS)
Temp (F)
Air Entering
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
3750/0.08 4300/0.09 5000/0.11 6250/0.13
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
172.0 156.3 144.2 132.3 174.3 160.0 148.4 136.2 177.4 162.8 150.6 138.2 183.6 169.0 157.5 145.6
SHC
41.4 66.6 87.6 112.1 43.2 72.5 94.8 121.3 43.6 76.9 99.6 127.5 65.5 87.0 115.5 142.7
kW
9.75 9.28 8.98 8.59 9.78 9.35 9.08 8.80 9.85 9.40 9.18 8.90 9.87 9.43 9.18 8.93
85
TC
164.0 147.6 136.2 123.7 165.4 150.7 140.1 127.2 154.1 140.8 127.9 161.1 148.0 135.4
SHC
41.9 58.7 80.0 103.8 43.2 63.5 86.5 112.2 68.7 91.0 118.1 77.7 107.8 133.2
kW
10.84 10.29 9.93 9.58 11.13 10.36 10.08 9.77 10.40 10.34 10.03 10.45 10.18 9.88
95
TC
155.5 138.9 128.2 115.1 141.4 131.8 118.3 145.3 131.0 117.6 153.1 138.4 125.1
SHC
35.1 50.8 72.3 95.5 54.4 78.1 103.2 60.5 82.3 108.7 68.5 100.0 123.7
kW
12.02 11.29 10.87 10.57 11.37 11.08 10.74 11.40 11.50 11.15 11.46 11.17 10.83
105
TC
129.1 117.8 105.8 131.7 121.0 108.7 134.8 119.9 107.7 140.9 126.9 115.9
SHC
42.1 63.5 86.5 45.4 69.0 93.9 51.2 74.2 101.3 57.7 90.2 113.6
kW
12.59 12.14 11.82 12.67 12.34 11.96 12.70 12.67 12.28 12.79 12.46 12.08
115
TC
119.2 107.3 96.4 122.1 110.2 99.0 124.2 108.8 97.8 128.7 115.3 106.7
SHC
33.5 54.8 77.5 36.4 59.8 84.7 41.9 66.1 93.8 46.8 80.5 103.5
kW
13.90 13.40 13.08 13.98 13.59 13.18 14.0 13.83 13.41 14.11 13.75 13.33
125
TC
109.4 96.9 87.1 112.4 99.4 89.3 113.7 97.7 87.8 116.5 103.8 97.5
SHC
24.8 46.0 68.5 27.4 50.7 75.5 32.6 58.0 86.4 36.0 70.7 93.5
kW
15.20 14.67 14.33 15.28 14.85 14.40 15.30 15.00 14.54 15.44 15.04 14.58
BF
Bypass Factor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Compressor Motor Power Input
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible heat capacity (Btuh)
1.1 x cfm
t
lwb
= wet-bulb temperature corresponding to
enthalpy of air leaving indoor coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
0TFQ004-012