Bryant 558F Air Conditioner User Manual


 
39
PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
Standard Ratings
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leaving evapora-
tor coil (h
lwb
)
Where: h
ewb
= Enthalpy of air entering evaporator coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 - BF) x (edb - 80).
558F121 (10 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
Air Entering Evaporator Cfm/BF
3000/0.095 4000/0.125 5000/0.15
Air Entering Evaporator Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC
136.6 125.5 112.7 143.2 131.4 120.5 147.4 135 124.4
SHC
67.2 83.1 98 73.6 93.9 113.4 80.2 105 123.8
kW
8.12 7.83 7.57 8.32 8 7.71 8.46 8.11 7.83
85
TC
130.8 120.3 104.6 136.8 125.7 115.2 140.8 128.7 119.5
SHC
64.7 81 94.4 71.5 92.2 110.8 78 102.4 119.4
kW
8.66 8.38 8.1 8.88 8.55 8.27 9.02 8.66 8.4
95
TC
124.8 114.4 97.3 130.3 119.6 107.5 133.6 122.7 114.8
SHC
62.6 78.9 90.5 69.5 90.3 106.5 75.3 100.7 114.7
kW
9.26 8.97 8.65 9.47 9.15 8.85 9.59 9.27 9.01
105
TC
118.8 105.2 88.4 123.4 112.5 99.1 126.7 115.8 108.6
SHC
60.8 75.3 85.7 67.3 88.2 99.1 73.5 98.9 108.6
kW
9.93 9.59 9.24 10.09 9.77 9.49 10.21 9.89 9.69
115
TC
115.7 98.6 84.7 120.7 104.4 93.9 123.3 110.4 103.4
SHC
59.7 72.8 83.9 66.8 85.3 93.9 73.2 97.5 103.4
kW
10.2 9.84 9.49 10.38 10.04 9.8 10.48 10.15 9.99
558F150 (12
1
/
2
TONS)
Temp (F
Air Entering
Condenser
(Edb)
Air Entering Evaporator Cfm/BF
3750/0.08 4500/0.09 5000/0.10 6250/0.12
Air Entering Evaporator Ewb (F)
72 67 62 72 67 62 72 67 62 72 67 62
75
TC
175.6 162.2 149.2 181.0 167.5 154.2 182.9 170.2 156.4 187.2 174.7 161.8
SHC
85.7 107.3 128.0 91.4 116.2 140.3 94.2 122.2 146.5 102.1 135.3 160.7
kW
11.16 10.85 10.57 11.32 11.00 10.69 11.37 11.07 10.73 11.49 11.19 10.87
85
TC
169.3 155.7 140.6 174.2 160.7 147.0 176.9 163.0 149.7 181.5 167.3 155.8
SHC
83.9 104.8 124.0 89.6 113.9 137.0 92.7 119.7 143.6 100.9 133.4 155.6
kW
12.15 11.78 11.42 12.31 11.94 11.58 12.39 12.01 11.63 12.53 12.14 11.82
95
TC
161.9 148.9 132.0 166.8
153.5 139.1 169.5 155.7 142.8 173.2 159.5 149.6
SHC
81.4 102.0 119.8 87.0 111.1 133.2 90.7 117.3 140.2 98.3 130.8 149.6
kW
13.12 12.72 12.28 13.30
12.89 12.46 13.40 12.97 12.56 13.54 13.11 12.78
105
TC
154.9 141.3 123.0 158.8 145.4 130.2 160.9 147.6 135.0 165.3 151.2 143.2
SHC
79.0 99.2 115.5 84.5 108.2 128.1 87.8 114.3 134.9 96.6 127.8 143.1
kW
14.16 13.66 13.17 14.31 13.82 13.35 14.38 13.91 13.48 14.58 14.07 13.77
115
TC
146.2 132.2 113.1 150.5 137.0 122.4 152.3 139.4 127.8 155.2 142.7 136.0
SHC
76.1 95.7 110.3 81.7 105.2 122.3 85.0 111.6 127.7 92.9 125.0 135.8
kW
15.09 14.57 14.07 15.30 14.76 14.25 15.37 14.87 14.43 15.49 15.02 14.73
BF
Bypass Factor
Edb
Entering Dry-Bulb
Ewb
Entering Wet-Bulb
kW
Compressor Motor Power Input
Ldb
Leaving Dry-Bulb
Lwb
Leaving Wet-Bulb
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible capacity (Btuh)
1.10 x cfm
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79 78 77 76 75 under 75
81 82 83 84 85 over 85
Correction Factor
.05
1.04 2.07 3.11 4.14 5.18
Use formula
shown below.
.10
.98 1.96 2.94 3.92 4.90
.20
.87 1.74 2.62 3.49 4.36
.30
.76 1.53 2.29 3.05 3.82
0TFQ004-012
558F036-150