PERFORMANCE DATA (cont)
COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY OPTION (cont)
Do not operate at these conditions.
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
where h
ewb
= enthalpy of air entering indoor coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC
.
Correction Factor = 1.10 x (1 BF) x (db 80)
551B072 (6 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
1800/0.05 2100/0.06 2400/0.06 3000/0.08
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
89.0 82.6 75.6 68.5 91.1 84.9 78.0 70.9 92.4 85.9 79.5 73.5 89.1 82.7 77.0
SHC
25.0 36.0 44.8 55.4 25.1 37.5 49.1 59.7 25.2 38.8 51.1 64.0 41.8 58.1 70.2
kW
4.80 4.60 4.52 4.36 4.86 4.67 4.57 4.46 4.89 4.70 4.57 4.45
4.77 4.61 4.51
85
TC
84.9 78.2 71.6 64.5 87.0 80.9 73.4 65.8 82.0 74.4 67.9 85.8 78.2 72.3
SHC
21.8 31.4 41.2 41.7 21.9 33.0 44.7 55.8 34.7 47.4 60.1 37.6 54.3 66.7
kW
5.40 5.16 5.03 4.89 5.46 5.22 5.11 4.96 5.26 5.09 4.97 5.32 5.17 5.04
95
TC
80.7 73.8 67.4 60.2 76.3 68.3 60.5 77.5 69.3 62.3 82.0 72.8 67.5
SHC
18.7 27.0 37.6 47.9 28.2 40.1 51.6 30.2 43.7 56.2 33.6 49.2 62.9
kW
6.01 5.75 5.60 5.44 5.80 5.66 5.48 5.84 5.68 5.53 5.90 5.73 5.60
105
TC
68.4 62.6 55.9 71.4 64.3 56.2 72.1 64.6 58.3 75.7 67.0 62.4
SHC
22.3 33.5 43.5 23.4 36.5 48.0 25.4 38.4 50.2 29.1 45.2 56.2
kW
6.37 6.22 6.06 6.45 6.27 6.10 6.46 6.29 6.16 6.53 6.36 6.24
115
TC
63.4 57.8 50.7 66.0 60.1 51.5 66.4 59.6 54.5 68.8 60.8 57.5
SHC
18.1 29.5 38.9 18.8 32.9 44.1 20.7 33.3 43.8 24.3 41.4 49.7
kW
7.04 6.89 6.68 7.10 6.91 6.74 7.12 6.95 6.83 7.16 7.01 6.92
125
TC
55.5 49.6 45.8 58.4 52.4 46.1 57.6 52.1 49.5 59.2 52.8 53.1
SHC
15.3 24.0 35.2 15.7 27.5 39.0 17.5 27.5 38.4 20.9 34.6 44.4
kW
7.80 7.61 7.38 7.83 7.67 7.49 7.89 7.72 7.58 7.92 7.78 7.70
551B090 (7
1
/
2
TONS)
Temp (F)
Air Entering
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
2250/0.095 3000/0.110 3750/0.135
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62
75
TC
104.4 98.4 91.1 81.1 109.5 103.7 97.9 91.8 110.0 105.8 101.3 94.1
SHC
31.1 44.5 55.4 67.0 34.0 50.4 65.4 80.5 36.5 54.5 72.4 89.5
kW
5.10 5.05 4.96 4.87 5.40 5.09 5.04 4.97 5.69 5.16 5.04 4.99
85
TC
99.9 94.2 85.8 76.9 106.8 100.3 92.4 85.2 109.6 103.5 96.8 89.0
SHC
27.4 39.7 51.3 62.7 30.9 46.2 58.3 75.7 31.5 50.6 68.2 84.3
kw
5.79 5.74 5.65 5.55 6.12 5.81 5.75 5.64 6.45 5.89 5.74 5.70
95
TC
97.6 89.9 80.5 72.6 104.2 96.9 86.8 78.6 107.9 101.1 92.2 83.8
SHC
24.4 34.8 47.2 58.3 27.7 41.9 51.2 71.0 28.9 46.6 63.9 79.1
kW
6.53 6.42 6.33 6.22 6.83 6.52 6.45 6.31 7.17 6.62 6.43 6.40
105
TC
91.7 84.6 75.3 68.0 91.6 81.3 73.4 94.5 86.3 78.4
SHC
20.7 30.0 42.5 53.9 36.9 49.3 66.4 41.4 59.2 73.8
kW
7.34 7.26 7.16 7.05 7.36 7.25 7.15 7.46 7.29 7.23
115
TC
79.2 70.1 63.3 86.2 75.8 68.1 87.9 80.3 72.9
SHC
25.2 37.8 49.4 31.9 47.4 61.9 36.1 54.4 68.5
kW
8.10 7.99 7.87 8.20 8.05 7.98 8.30 8.14 8.05
125
TC
72.8 64.5 57.2 78.0 69.8 62.3 81.6 73.2 69.2
SHC
20.1 33.4 44.1 25.4 42.5 56.5 31.1 48.9 64.7
kW
9.10 8.94 8.83 9.23 9.05 8.95 9.26 9.10 8.99
551B102 (8
1
/
2
TONS)
Temp (F)
Air Entering
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
2550/0.075 3000/0.09 3400/0.105 4250/0.125
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
120.5 112.4 102.2 92.6 121.5 115.2 106.4 96.4 124.9 119.6 110.3 101.3 132.7 127.6 117.6 108.0
SHC
32.5 49.1 62.4 75.0 33.2 52.9 68.5 82.3 34.2 56.2 73.3 89.5 38.0 62.8 83.3 101.7
kW
6.16 6.10 5.96 5.86 6.41 6.18 6.05 5.95 6.53 6.18 6.05 5.95 6.83 6.18 6.10 6.00
85
TC
114.2 105.7 95.7 86.5 116.7 110.0 100.6 91.0 120.3 114.0 103.7 94.6 124.0 120.3 110.9 101.2
SHC
28.8 43.6 57.1 69.9 29.9 47.8 62.8 76.9 30.4 50.7 67.9 82.8 44.8 58.5 77.7 98.4
kW
6.99 6.92 6.78 6.63 7.20 6.97 6.90 6.75 7.37 7.01 6.85 6.75 7.68 7.01 6.91 6.80
95
TC
108.0 98.9 89.1 80.4 112.4 104.7 94.8 85.5 115.0 108.4 97.0 87.9 113.0 104.1 94.3
SHC
25.1 38.0 51.7 64.8 26.8 42.7 57.0 71.4 27.2 45.2 62.4 76.2
54.3 72.0 87.9
kW
7.85 7.73 7.59 7.40 8.03 7.75 7.75 7.56 8.21 7.84 7.65 7.54 7.84 7.71 7.60
105
TC
100.2 91.8 82.3 73.8 97.3 87.6 78.6 100.4 89.8 80.8 105.1 95.3 85.8
SHC
20.9 32.6 46.3 59.5 37.0 51.9 66.8 39.3 56.7 70.0 47.1 65.5 80.9
kW
8.91 8.80 8.64 8.47 8.80 8.76 8.58 8.89 8.69 8.59 8.93 8.77 8.67
115
TC
84.7 75.5 67.3 89.8 80.5 71.7 82.5 82.5 73.8 97.2 86.6 77.4
SHC
27.2 40.9 54.2 31.4 46.9 62.2 33.4 51.0 63.8 39.9 59.1 73.9
kW
9.86 9.69 9.53 9.86 9.77 9.61 9.95 9.74 9.65 10.01 9.84 9.75
125
TC
77.6 68.7 60.7 82.4 73.3 64.8 84.5 75.3 66.7 89.3 77.8 68.9
SHC
21.8 35.5 48.9 25.7 41.8 57.6 27.5 45.3 57.6 32.7 52.6 66.9
kW
10.93 10.74 10.60 10.91 10.78 10.64 11.00 10.78 10.70 11.10 10.90 10.82
BF
Bypass Factor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Compressor Motor Power Input
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible heat capacity (Btuh)
1.1 x cfm
t
lwb
= wet-bulb temperature corresponding to
enthalpy of air leaving indoor coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
0TFQ004-012
551B036-150