Bryant 558F Air Conditioner User Manual


 
64
PERFORMANCE DATA (cont)
ELECTRIC HEATING CAPACITIES
*Two heater packages required to provide kW indicated.
009 for 558F102 units.
**On units with factory-installed outlet, use CRSINGLE014A00.
NOTES:
1. The kW ratings shown above are at 240, 480, and 600 v. Use the Multiplica-
tion Factors table below to determine heater capacity for your particular
voltage.
MULTIPLICATION FACTORS
Example: 32.0 kW (at 240 v) heater on 208 v
= 32.0 (.75 mult factor)
= 24.0 kW capacity at 208 v
2. Heaters are not available for size 036-072 575-v units.
UNIT
558F
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY
SINGLE POINT BOX
PART NO.
CRSINGLE---A00
036
208/230
(single
phase)
4.4 101
6.5 102
8.7 103
10.5 104
13.0* 102* 004
208/230
(3 phase)
4.4 101
6.5 102
8.7 103
10.5 104
16.0 105
460
(3 phase)
6.0 106
8.8 107
11.5 108
14.0 109
048
208/230
(single
phase)
4.4 101
8.7 103
13.0* 102* 004
17.4* 103* 004
21.0* 104* 004
208/230
(3 phase)
6.5 102
8.7 103
16.0 105
21.0* 104* 002
460
(3 phase)
6.0 106
11.5 108
14.0 109
23.0* 108*
060
208/230
(single
phase)
6.5 102
8.7 103
13.0* 102* 004
17.4* 103* 004
21.0* 104* 004
208/230
(3 phase)
6.5 102
10.5 104
16.0 105
21.0* 104* 002
26.5* 105,104 002
460
(3 phase)
6.0 106
11.5 108
14.0 109
23.0* 108*
25.5* 109,108
072
208/230
(3 phase)
6.5 102
10.5 104
16.0 105
21.0* 104* 002
26.5* 105,104 002
460
(3 phase)
6.0 106
11.5 108
14.0 109
23.0* 108*
25.5* 109,108
UNIT
558F
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY
SINGLE POINT BOX
PART NO.
CRSINGLE---A00
090,
102
208/230
(3 phase)
10.5 117 006
16.0 110 006
24.8 111 007
32.0 112 007
42.4* 112,117 007
460
(3 phase)
14.0 116 006
16.5 113 006
27.8 114 006
33.0 115 006
41.7* 114,116 008
575
(3 phase)
17.0 118 006
34.0 119 006
120,
150
208/230
(3 phase)
10.5 117 012
16.0 110 012
32.0 112 012
42.4* 112,117 015
50.0* 112,110 015
460
(3 phase)
16.5 113 011
27.8 114 011
33.0 115 011**
41.7* 114,116 014
50.0* 115,113 014
575
(3 phase)
17.0 118 011
34.0 119 011
51.0* 119,118 014
HEATER kW
RATING
VOLTAGE DISTRIBUTION
V/3/60
MULTIPLICATION
FAC TO R
240
200
208
230
240
.69
.75
.92
1.00
480
440
460
480
.84
.92
1.00
600
550
575
600
.84
.92
1.00
0TFQ004-012
558F036-150