Bryant 558F Air Conditioner User Manual


 
67
ELECTRICAL DATA 558F036-073 (cont)
See Legend and Notes on page 70.
UNIT
558F
NOMINAL
V-Ph-Hz
IFM
TYPE
VOLTAGE
RANGE
COMPRESSOR
(ea)
OFM
(ea)
IFM
FLA
ELECTRIC
HEAT*
POWER
SUPPLY
DISCONNECT
SIZE
Min Max RLA LRA Qty Hp FLA
Nominal
kW**
FLA MCA MOCP†† FLA LRA
072,
073
208/230-3-60
Std
187 254 20.6 146 1
1
/
4
1.4
5.2
——32.4/32.4 40/40 31/31
180/180
4.9/ 6.5 13.6/15.6 32.4/32.4 40/40 31/31
7.9/10.5 21.9/25.3 33.9/38.1 35/40 31/35
12.0/16.0 33.4/38.5 48.2/54.6 50/60 44/50
15.8/21.0 43.8/50.5 61.2/69.6 70/70|| 56/64
19.9/26.5 55.2/63.8 75.6/86.2 80/90|| 70/79
High 7.5
——34.7/34.7 40/40 34/34
205/205
4.9/ 6.5 13.6/15.6 34.7/34.7 40/40 34/34
7.9/10.5 21.9/25.3 36.7/40.9 40/45 34/38
12.0/16.0 33.4/38.5 51.1/57.5 60/60 47/53
15.8/21.0 43.8/50.5 64.1/72.5 70/80|| 59/67
19.9/26.5 55.2/63.8 78.4/89.1 80/90|| 72/82
460-3-60
Std
414 508 9.5 73 1
1
/
4
0.9
2.6
——15.4 20 15
90
6.0 7.0 15.4 20 15
11.5 14.0 20.5 25 19
14.0 17.0 24.3 25 22
23.0 28.0 37.8 40 35
25.5 31.0 41.6 45 38
High 3.4
——16.2 20 16
103
6.0 7.0 16.2 20 16
11.5 14.0 21.5 25 20
14.0 17.0 25.3 30 23
23.0 28.0 38.8 40 36
25.5 31.0 42.6 45 39
575-3-60
Std
518 632 7.6 58.4 1
1
/
4
0.9
2.6 ——13.0 15 13 75
High 3.4 ——13.8 20 14 88
0TFQ004-012
558F036-150