Bryant 558F Air Conditioner User Manual


 
79
PERFORMANCE DATA
COOLING CAPACITIES, STANDARD UNITS
Do not operate at these conditions.
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
where h
ewb
= enthalpy of air entering indoor coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC
.
Correction Factor = 1.10 x (1 BF) x (db 80)
551B036 (3 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
900/0.14 1200/0.17 1500/0.20
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62
75
TC
45.6 41.9 38.7 35.7 46.8 43.5 40.8 37.7 48.1 44.8 41.8 39.0
SHC
14.5 20.4 25.2 29.7 14.7 21.8 28.2 33.8 14.8 23.3 30.7 37.0
kW
2.24 2.19 2.16 2.12 2.26 2.21 2.18 2.15 2.28 2.23 2.19 2.16
85
TC
44.4 40.7 37.5 34.5 45.7 42.1 39.3 36.4 47.0 43.5 40.4 37.6
SHC
14.1 19.9 24.7 29.2 14.4 21.5 27.7 33.2 14.8 23.2 30.3 36.4
kW
2.51 2.46 2.42 2.39 2.53 2.47 2.44 2.41 2.54 2.50 2.45 2.42
95
TC
42.9 39.3 36.1 33.1 44.6 40.8 37.8 34.9 42.0 38.9 36.1
SHC
13.6 19.5 24.1 28.4 14.0 21.1 27.2 32.5 22.8 29.9 35.6
kW
2.80 2.75 2.71 2.66 2.83 2.77 2.73 2.69 2.79 2.74 2.71
105
TC
41.3 37.7 34.6 31.7 39.3 36.2 33.4 40.1 37.2 34.7
SHC
13.0 18.8 23.5 27.8 20.7 26.6 31.8 22.1 29.3 34.7
kW
3.11 3.06 3.02 2.98 3.09 3.04 3.01 3.10 3.06 3.03
115
TC
36.0 33.0 29.7 37.4 34.5 31.5 38.1 35.5 33.2
SHC
18.3 22.9 26.7 19.9 26.1 30.9 21.3 28.7 33.2
kW
3.41 3.36 3.31 3.43 3.39 3.34 3.44 3.41 3.37
125
TC
34.2 31.3 27.8 35.6 32.7 29.4 36.3 33.6 31.9
SHC
17.6 22.2 25.8 19.4 25.4 29.4 20.8 28.0 31.8
kW
3.78 3.73 3.66 3.80 3.76 3.71 3.81 3.78 3.75
551B048 (4 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
1200/0.17 1450/0.19 1600/0.21 2000/0.24
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
58.6 54.0 50.7 44.2 59.6 55.9 52.2 47.7 59.9 56.4 52.8 49.1 61.5 58.1 54.5 50.6
SHC
18.3 26.1 32.7 37.5 18.7 27.6 35.1 41.8 18.7 28.2 36.2 43.8 19.2 30.2 39.5 47.5
kW
2.80 2.80 2.80 2.80 2.90 2.80 2.80 2.80 2.90 2.80 2.80 2.80 2.90 2.80 2.80 2.80
85
TC
56.4 52.2 48.9 41.9 57.3 54.1 50.4 45.9 58.1 54.5 51.0 47.2 59.5 55.3 52.3 48.7
SHC
17.6 25.4 32.0 36.4 17.9 26.9 34.5 40.8 18.2 27.5 35.7 42.8 18.5 28.6 38.5 46.6
kW
3.30 3.20 3.20 3.20 3.30 3.20 3.20 3.20 3.30 3.20 3.20 3.20 3.30 3.20 3.20 3.20
95
TC
54.2 50.7 46.9 39.5 55.0 51.9 48.4 43.5 56.3 52.5 48.9 45.2 57.5 53.9 50.1 46.7
SHC
16.9 24.9 31.1 35.0 17.2 26.1 33.6 39.6 17.6 26.8 34.7 41.8 17.8 28.8 37.5 45.6
kW
3.70 3.60 3.60 3.60 3.70 3.70 3.60 3.60 3.70 3.70 3.60 3.60 3.70 3.70 3.60 3.60
105
TC
52.0 48.8 44.5 36.7 52.7 49.8 46.2 40.7 53.8 50.2 46.7 42.1 54.7 51.5 48.2 44.7
SHC
16.2 24.3 30.2 33.6 16.5 25.3 32.8 38.2 16.8 26.0 33.9 40.3 17.1 27.9 37.4 44.4
kW
4.20 4.10 4.10 4.00 4.20 4.10 4.10 4.10 4.20 4.10 4.10 4.10 4.20 4.10 4.10 4.10
115
TC
49.9 46.5 41.1 34.3 50.4 47.7 43.3 37.0 41.3 48.0 44.4 38.5 51.9 48.9 45.7 42.0
SHC
15.5 23.4 28.9 32.4 15.8 24.9 31.8 36.3 16.0 25.4 33.4 38.3 16.3 27.1 36.9 42.0
kW
4.70 4.60 4.60 4.50 4.70 4.70 4.60 4.60 4.70 4.60 4.60 4.60 4.70 4.70 4.60 4.60
125
TC
47.5 43.8 37.5 32.4 45.1 39.0 33.8 45.3 40.1 35.4 46.3 42.6 38.8
SHC
15.0 22.5 27.4 31.5 24.1 30.2 33.7 24.7 31.9 35.4 26.5 35.9 38.8
kW
5.20 5.20 5.10 5.10 5.20 5.20 5.10 5.20 5.20 5.10 5.20 5.20 5.20
551B072 (5 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
1500/0.08 1750/0.09 2000/0.11 2500/0.13
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
80.4 70.8 65.4 58.5 82.5 72.5 67.3 61.1 83.7 73.0 68.4 62.8 74.870.364.8
SHC
25.6 34.1 42.7 49.9 26.1 35.7 45.5 54.2 26.3 36.8 48.0 57.8 39.653.063.4
kW
3.65 3.53 3.49 3.44 3.68 3.55 3.50 3.46 3.70 3.55 3.51 3.47 3.57 3.54 3.48
85
TC
78.5 68.9 63.2 55.3 70.5 65.1 57.9 72.2 66.4 60.2 73.268.162.9
SHC
25.1 33.5 41.8 48.4 35.0 44.8 52.8 37.0 47.6 56.8 39.352.562.4
kW
4.20 3.98 3.94 3.87 4.00 3.96 3.90 4.03 3.97 3.92 4.04 3.99 3.94
95
TC
66.8 60.6 52.4 68.3 62.5 54.3 69.3 63.8 56.6 71.265.660.6
SHC
32.8 40.7 47.0 34.5 43.8 51.1 36.0 46.7 55.0 39.151.860.5
kW
4.48 4.43 4.35 4.50 4.45 4.37 4.51 4.46 4.40 4.55 4.48 4.44
105
TC
64.3 57.7 49.9 65.9 59.8 51.7 66.9 61.1 54.1 68.462.858.4
SHC
32.0 39.6 45.8 33.7 42.8 49.7 35.3 45.7 53.5 38.451.058.4
kW
5.03 4.96 4.87 5.05 4.99 4.90 5.06 5.00 4.93 5.08 5.02 4.98
115
TC
61.5 54.8 47.3 62.8 56.7 49.1 64.0 58.2 51.6 65.459.956.1
SHC
31.0 38.4 44.5 32.5 41.6 48.2 34.4 44.6 51.6 37.450.056.1
kW
5.61 5.55 5.46 5.62 5.58 5.49 5.65 5.60 5.52 5.67 5.61 5.57
125
TC
58.7 51.6 44.5 59.9 53.4 46.2 60.8 54.9 49.0 62.256.853.5
SHC
30.0 37.2 43.1 31.7 40.4 46.2 33.3 43.4 48.9 36.448.953.4
kW
6.27 6.19 6.09 6.28 6.21 6.13 6.29 6.24 6.17 6.31 6.27 6.22
BF
Bypass Factor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Compressor Motor Power Input
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible heat capacity (Btuh)
1.1 x cfm
t
lwb
= wet-bulb temperature corresponding to enthalpy of
air leaving indoor coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
0TFQ004-012
551B036-150