Legend and Notes for Table 5
LEGEND:
BRKR --- Circuit breaker
CO --- Convenient outlet
DD --- Direct drive
indoor fan motor
DISC --- Disconnect
FLA --- Full load amps
IFM --- Indoor fan motor
LRA --- Locked rotor amps
MCA --- Minimum circuit amps
PE --- Power exh aust
PWRD CO --- Powered convenient outlet
UNPWR CO --- Un powered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is g reater than 2%. Use the following f ormula to de-
termine the percentage of voltage imbalance.
% VoltageImbalance =100 x
max voltage deviation fromaverage voltage
averagevoltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 +231 + 226)
=
681
3
3
= 227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v Maximum deviation is 4 v...........
(BC) 231 – 227 = 4 v Determine percent of voltage imbalan ce...........
% VoltageImbalance = 100 x
4
227
=1.76%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.
C09302
Fig. 54 -- EconoMi$er IV Wiring
Step 11 — Adjust Factory--Installed Options
Smoke Detectors —
Smoke detector(s) will be connected at the Controls
Connections Board, at terminals marked “Smoke
Shutdown”. Cut jumper JMP 3 when ready to energize
unit.
EconoMi$er IV Occupancy Switch —
Refer to Fig. 56 for general EconoMi$er IV wiring.
External occupancy control is managed through a
connection on the Controls Connections Board.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked
OCCUPANCY. Cut jumper JMP 2 to complete the
installation.