Single Point Boxes and Supplementary Fuses When
the unit MOCP device value exceeds 60--A, unit--mounted
supplementary fuses are required for each heater circuit.
These fuses are included in accessory Single Point Boxes,
with power distribution and fuse blocks. The single point
box will be installed directly under the unit control box,
just to the left of the partition separating the indoor
section (with electric heaters) from the outdoor section.
The Single Point Box has a hinged access cover. See
Fig. 27. The Single Point Box also includes a set of
power taps and pigtails to complete the wiring between
the Single Point Box and the unit’s main control box
terminals. Refer to the accessory heater and Single Point
Box installation instructions for details on tap
connections.
All fuses on 551J units are 60--A. (Note that all heaters are
qualified for use with a 60--A fuse, regardless of actual
heater ampacity, so only 60--A fuses are necessary.)
Single Point Boxes without Fuses Unit heater
applications not requiring supplemental fuses require a
special Single Point Box without any fuses. The accessory
Single Point Boxes contain a set of power taps and pigtails
to complete the wiring between the Single Point Box and
the unit’s main control box terminals. Refer to accessory
heater and Single Point Box installation instructions for
details on tap connections.
A
L
L
I
E
D
P
A
M
O
D
E
L
N
O
.
ER
I
A
L
N
O.
C
O
R
P
.
11
13
21
23
O
D
2
2
.
2
3
1
2
3
ISTED
AI
R
NDITIONING
UIP
ACCESS
3
4
6
N
.
P
/
N
2-
5
6
10-
4
REV
1
1
13
2
1
2
3
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
FOAM
BUSHING
DRIP BOOT
BRACKET
MOUNTING
SCREWS
HEATER
RELAYS
POWER
WIRES
HEATER
MOUNTING
SCREWS
C08136
Fig. 27 -- Typical Single Point Installation
Low--Voltage Control Connections Pull the
low--voltage control leads from the heater module(s) --
VIO and BRN (two of each if two modules are installed;
identify for Module #1) -- to the 4--pole terminal board
TB4 located on the heater bulkhead to the left of Heater
#1. Connect the VIO lead from Heater #1 to terminal
TB4--1. For 2 stage heating, connect the VIO lead from
Heater #2 to terminal TB4--2. For 1 stage heating with 2
heater modules connect the VIO lead from both Heater #1
and #2 to terminal TB4--1. Connect both BRN leads to
terminal TB4--3. See Fig. 28.
ORN
BRN
Field
Connections
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
2
3
12
13
VIO
ORN
VIO
BRN
VIO
BRN
BRN
VIO
2
TB4
VIO
HR2
HR1
BRN
VIO
BRN
Elec Htr
CTB
CONTL
BOARD
C08331
Fig. 28 -- Accessory Electric Heater Control
Connections
551J