Table 6 indoor-Fan Motor Performance
LEGEND
BHP
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using fan motors up to the horsepower ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
Table 7 Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown.
Indicates standard motor and drive package.
**Indicates alternate drive package only.
††Indicates alternate motor and drive package.
UNIT
548D
INDOOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
090
Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
102
Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
120
Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
Alternate
208/230
2.90 2615
7.9
460 3.6
575 3.6
UNIT
548D
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
5
090
840 815 790 765 740 715 690 665 635 615 590
090**
935 910 885 860 835 810 785 760 735 710 685
102
935 910 885 860 835 810 785 760 735 710 685
120
935 910 885 860 835 810 785 760 735 710 685
120††
1085 1060 1035 1010 985 960 935 910 885 860 835