Bosch Appliances FMR-1000-RCMD Smoke Alarm User Manual


 
Remote Command Center Troubleshooting | en 15
Bosch Security Systems, Inc. Installation and Operation Guide F.01U.078.098 | 3.0 | 2011.11
pattern, or they fully de-energize, as defined by the global option “Silence Config”. Strobes
continue flashing.
If programmed, the panel transmits a silence report to the central station.
If the panel is already silenced, pressing [SILENCE] again causes an unsilence command in the
panel. Silence operation does not reset the alarm status and does not return the activated
input to normal service. Any new alarm reactivates any silenced outputs.
Trouble Reminder
If any events are not cleared within 24 hours after the [SILENCE] or [ACK] key was pressed,
the panel turns on the piezo again and events are transmitted to the central station again.
Reset
Pressing the reset key turns off the piezo and all activated or silenced outputs. The reset
operation turns off auxiliary power AUX/RST for 5 seconds, and activates the global resetting
zone. All alarms, supervisories, and troubles caused by activation of SLC points are cleared.
Then the panel tries to reset all points that are in off-normal status. Not all system trouble
conditions are affected by the reset operation. If programmed, the panel transmits a reset
report to the central station.
Any alarm or trouble that exists after a reset causes the system to sound again.
Drill
To activate the drill operation, the [DRILL] key must be pressed twice to prevent accidental
activation. Pressing the key once the system prompts for confirmation. Pressing the [DRILL]
key again turns on all unbypassed NACs and drillable relay outputs.
The drill operation stops if the reset key is pressed, or it is automatically cancelled if the
operation was started for a programmed time. A system reset is automatically performed by
stopping the drill so that the panel and all field devices restore to their normal operation.
If programmed, a drill start report and a drill stop report are transmitted to the central
station.
10 Troubleshooting
11 Specifications
11.1 Electrical
Display LED Piezo Description
NOT PROGRAMMED 0.5 s on/
0.5 s off
0.5 s every
10 s
No communication activities on
the device address.
NO COMMUNICATION 0.5 s on/
0.5 s off
0.5 s every
10 s
After 60 seconds of no
communication activities on any
Option Bus address.
COMMUNICATION OK off off Communication on the device
address; no text received yet.
Operating voltage Nominal 12 V DC or 24 V DC/FWR
Current consumption at 12 V DC
Standby current 25 mA maximum (only Power LED on)
Alarm current 150 mA maximum (with annunciator lit and piezo
on)