Remote Command Center Operating | en 13
Bosch Security Systems, Inc. Installation and Operation Guide F.01U.078.098 | 3.0 | 2011.11
Table 9.1 LED Operation
Display
The FMR-1000-RCMD Remote Command Center uses an 80-character (4 lines x 20 characters)
wide viewing-angle LCD display. The display includes a long-life LED backlight. The backlight
is controlled by the panel, or locally turned on upon any key press and turned off after
30-second time-out without key press. Even when AC power is lost, the LED backlight remains
lit if a user is operating the keypad.
Piezo Sounder
The FMR-1000-RCMD Remote Command Center has a piezo that provides audible indication
of the system status. Refer to Table 9.2 for piezo modes when FMR-1000-RCMD is controlled
by the panel:
Table 9.2 Piezo Operation with FMR-1000-RCMD Panel Controlled
In case of multiple piezo activation, the system status with highest priority is indicated.
If the Remote Command Center is not controlled by the panel or during a communication
fault, refer to Table 9.3 for piezo modes:
Table 9.3 Piezo Operation with FMR-1000-RCMD Controlled Locally
Trouble
Yellow
On – When the panel is initializing
– When the panel registers a trouble condition from a point, or the panel
– When inputs or outputs or other elements are bypassed
Flashing
1)
– When the panel is not operating
– When walk test is in progress
Off – When no trouble condition exists
– When the panel is resetting
1)
LED flash rate is 1 Hz (0.5 s on, 0.5 s off).
LED System Status
Piezo Operation System Status
Silent The panel is in a normal state (no alarm, supervisory or trouble
condition). The panel was silenced or acknowledged after an off-
normal condition.
Continuous beep The panel is in fire alarm condition.
Periodic beep
(0.5 s every 2 s)
The panel is in gas alarm condition.
Periodic beep
(0.5 s every 4 s)
The panel is in supervisory condition.
Periodic beep
(0.5 s every 10 s)
The panel is in trouble condition or a communication fault exists
on the Option Bus.
Short beep With every valid key press.
Piezo Operation System Status with FMR-1000-RA Controlled Locally
Periodic beep
(0.5 s every 10 s)
A communication fault exists on the Option Bus.