Page 50 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide
10.20 Timer Programming: Program Addresses (4028-4030, 4032-4033)
10.21 AC Fail Report Delay Programming: Program Address (4034)
The AC Fail Delay Times are programmed as Hexadecimal values.
For example:
00 = Send only with next report
1 *4 = 30 minute delay
3 *2 = 60 minute delay
78 = 120 minute delay
*5 0 = 240 minute delay
*5 *5 = Random delay (at least 15 minutes, but less than 120 minutes)
(*0 - *5 are Hex values. They will display as A through F at the keypads.)
See Glossary (section 6.13) for further details.
0 to 99 minutes* Default = 04 minute
s
*1 minute intervals; 99 = 30 second cutoff
0 to 51 (0 to 255 sec.*) Default = 09 (45 sec.)
Data Digit
12
Address 4028
Entry Delay Time 1
Data Digit
12
Address 4029
Entry Delay Time 2
Data Digit
12
Address 4030
Exit Delay Time
Data Digit
12
Address 4032
Fire Bell Cutoff
Data Digit
12
Address 4033
Burglary Bell Cutoff
May be forced to a different value when in
Commercial Fire Mode.
See section 10.18.3
.
0 to 51 (0 to 255 sec.*) Default = 09 (45 sec.)
*5 second intervals
*5 second intervals
0 to 51 (0 to 255 sec.*) Default = 12 (60 sec
.)
*5 second intervals
0 to 99 minutes* Default = 04 minute
s
*1 minute intervals; 99 = 30 second cutoff
Entry and Exit Delay Timers are in
5 second intervals (the maximum
delay time is 255 seconds).
For example:
5 sec. = 01
15 sec. = 03
20 sec. = 04
30 sec. = 06
45 sec. = 09
60 sec. = 12
255 sec. = 51