Bosch Appliances DS7400XI Home Security System User Manual


 
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 21
- Smoke alarm. This must be the odd numbered zone of the
zone pair required for these devices. The zone must be
programmed with a zone function that is set for Fire Zone and
Trouble onOpen.
- Low Temperature Alarm. This must be the even numbered
zone of the zone pair required for these devices. This zone
must be programmed with a zone function that is set as
Supervisory and Trouble on Open.
6.4 Output Programming
Latch on Any Zone Alarm: This is an output programmed to
activate upon any zone alarm (including invisible zones) and will
latch until the system has been disarmed.
- If this output is programmed to respond only to a fire zone, it
will remain latched until the fire reset command is performed.
ON during Entry Pre-Alert: This is an output programmed to
activate when an entry/exit zone is violated while the system is
armed.
- It will remain activated until the system is disarmed, or until
the entry delay time has expired.
ON for 10 seconds after [PIN] + [System Reset] is entered: This
is an output programmed to activate for 10 seconds after the fire
reset command is entered at the keypad or if a Fire Zone with
Verification activates.
- This output is intended to be used to power 4-wire smoke
detectors or any other device that requires a power interruption
to reset an alarm condition.
NOTE: When Programmable Output 2 is programmed this way,
it will normally supply auxiliary power and will turn OFF for
10 seconds when the fire reset command is entered.
ON when System is Armed: This is an output programmed to
activate when the system is armed.
- It will remain activated until the system is disarmed.
Ground Start: This is an output programmed to activate for 3
seconds when the phone line is seized. It is intended for use
with ground start phone systems that require a momentary short
to ground to obtain a dial tone.
- Connect a separate 12 VDC, DPDT relay.
- Connect both relay contact commons to ground, and connect
the Normally Open of each contact to terminal positions 13
and 16 (one to terminal 13, the other to 16) of the DS7400Xi.
- This output follows all partitions regardless of how data digit 2
of the output programming address is programmed.
- Not intended for UL Listed systems. Not for use with phone
line monitors.
System Status (ready to arm): This is an output programmed
to follow the Status LED of the keypad.
- It will activate when the system is ready to arm with no zones
violated.
Zone Alarm: This is an output programmed to activate when a
zone is in an alarm condition.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens.
- This will not activate from Silent or Invisible Zones.
Zone Alarm Delayed by 20 sec.: This is an output programmed
to wait 20 seconds after a zone enters an alarm condition to
activate.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens, but
provides a delay to allow the user to silence the system before
it activates.
Output Functions
Output Functions can be programmed to follow system events
or to follow one or two specific zones in a “cross-matrix” fashion
(see Input/Output Cross-Matrixing).
- These Output Functions can be programmed to control Octal
Relay outputs or Multiplex Bus outputs.
- Output Functions are programmed in addresses 2772-2843.
Input/Output Cross Matrixing
Input/Output Cross Matrixing allows Output Functions to follow
the status of specific input zones (zones 1 through 248 only).
- Outputs can be programmed to follow any combination of one
or two zones, open or closed, with the system armed or dis-
armed.
- If programmed to latch, the output will latch until a valid PIN is
entered at the keypad.
Keypad Sounder Output: This is an output programmed to follow
the keypad sounder.
- It activates during the entry pre-alert and during any day monitor
alarm. It does not follow momentary keypad beeps such as
keystrokes, chimes, etc.
Access Output: This is an output programmed to activate for
10 seconds when an access control PIN is entered at the keypad.
- Not UL Listed for Access Control (UL294).
Panic/Duress Output: All outputs, including the three on-board
outputs, the Octal Relays, and the Output Functions, support a
Panic/Duress function. This output will follow Duress activations,
Keypad Emergency Keys B and C, and Invisible and Silent Zone
alarms. It will only be reset by a user acknowledgement and will
not reset after the burglary bell time-out occurs. Duress activa-
tions will latch until acknowledged by a user.
Multiplex Bus Outputs
The DS7400Xi supports up to 60 DS7465 Input/Output Modules.
- These modules are connected to the multiplex bus and provide
one input loop and one Form “C” output relay.
- The input loop operates the same as all other multiplex inputs.
- The output loop can be programmed to follow Output
Functions.
- Multiplex Bus outputs can be bypassed using the bypass
function. If an output zone is bypassed while it is ON, it will turn
OFF. The bypass will not be removed when the system is
armed and then disarmed; it must be cancelled by entering
the bypass command again or by cancelling all bypasses.
NOTE: DS7465 Module outputs will not pulse, even if programmed
to do so.
Octal Relay Modules (DS7488)
The DS7400Xi can support two Octal Relay Modules.
- Each relay can be programmed to follow system-wide events
or Output Functions as described above.
Solid State Output Modules (DS7489)
The DS7400Xi can support two Solid State Output Modules.
- Each output can be programmed to follow system-wide events
or Output Functions as described above.
6.5 Partition Control Programming
Partition Control Programming: Up to eight partitions may be
used. They are assigned (program address 3420) in order.