Beckett 7600 Boiler User Manual


 
5
AquaSmart Boiler Control Manual
AquaSmart Models and Cross-Reference Guide
Table 1a - Direct Replacements
Honeywell
Beckett
Replacement
Notes
L7148F (All)
L8148E (All)
7600B
Must con rm that 7600 VA rating is adequate to meet VA requirements of system.
Make sure 7600 B1 output does not exceed 1.25A @ 24VAC (30 VA).
7600 outputs are not rated for 240 VAC.
B2, TW and TR terminals replace TV, T and Z, respectively.
L8124A (All)
L8124C (All)
7600A
7600 outputs are not rated for 240 VAC.
L7124A/C (All)
L7148A (All)
L7224
A/C/U
(All)
L7248A/C (All)
7600A
The 7600 has no Honeywell EnviraCOM
TM
Communications port.
The diagnostic LED lights are replaced by the 7600’s display.
L8148A (All) 7600A
7600 outputs are not rated for 240 VAC.
B1 terminal on 7600 utilizes a 1/4” quick connect.
Set low limit on 7600 to OFF.
L8124E 1016
L8148E 1265
7600B
7600 outputs are not rated for 240 VAC.
B2, TW and TR terminals replace TV, T and Z, respectively.
L8124M (All) 7600A
For replacement with the 7600: Turn low limit off so the circulator is controlled directly by the thermostat and ZC is constantly powered.
L8151A 7600A
7600 outputs are not rated for 240 VAC.
Remote mount sensor cable needed (Part No. 52120)
Hydrolevel
Beckett
Replacement
Notes
3100 7600B
Not a suitable replacement if Low Water Cutoff (LWCO) functionality of the 3100 is used.
3150 7600A
Not a suitable replacement if Low Water Cutoff (LWCO) functionality of the 3150 is used.
Carlin
Beckett
Replacement
Notes
90524A 7600A
Make sure 7600 outputs do not exceed 7.4A.
Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.
The diagnostic LED lights are replaced by the 7600’s display.
White Rodgers
Beckett
Replacement
Notes
11C15-11 7600A
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
8B48A-217 7600A
11C30-3
11B54-4
7600A
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing.
8F48A-351
8B43A-601
7600B
11C61-12 7600A
Not a suitable replacement if SPDT switch action is required; only break-on-rise available on 7600.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
Table 1b - Functional Replacement (Advanced Wiring Needed)
Honeywell
Beckett
Replacement
Notes
L4006A (All)
L4006G 1022
L4006H 1004
L4008A (All)
L4080B/D
7600A or 7600B
(Based on System
Voltage
Requirements)
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Set low limit on 7600 to OFF.
Available operating limit and/or differential ranges may not be equivalent. Compare the settings to the AquaSmart ranges before replacing.
To use with a millivolt system, an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit.
L4006E (All)
L4008E (All)
L4080F/G
7600A or 7600B
(Based on System
Voltage
Requirements)
Requires the addition of a manual-reset high limit.
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC.
7600 will require an additional wire (L2) for operation. Short TW-TR terminals. C1, C2, ZC, and ZR are unused.
Set low limit on 7600 to OFF.
Available operating limit and/or differential ranges may not be equivalent. Compare the settings to the AquaSmart ranges before replacing.
To use with a millivolt system, an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit.
(Table continued on next page)
Burn, Scald, Explosion, and Equipment Malfunction Hazard
Replacement of the following controls must be done only by a quali ed service agency or technician who is
trained and experienced in the use of boiler controls.
Carefully follow these guidelines and the directions provided by the manufacturer of the control being replaced.
Note: Beckett assumes no liability for incorrect installation or replacement.