Bacharach AGM300 Smoke Alarm User Manual


 
Instruction 3015-4275 43
Spill Level
This is the concentration level in PPM that will activate a spill alarm condition.
1. Press the SPILL LEVEL key to adjust the value.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
NOTE: This value must be less than the evacuate level and greater than the leak level.
Evacuation Level
This is the concentration level in PPM that will activate an evacuate alarm condition.
1. Press the EVAC LEVEL key to adjust the value.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
NOTE: This value must be greater than the spill level.
Re-Setting the Peak PPM Value
Pressing this key resets the current peak PPM level stored in memory and displays it at the top of the screen.