Bacharach AGM300 Smoke Alarm User Manual


 
Instruction 3015-4275 31
Display
showing
“WARM UP”
ADM800 - Screen Displays
When first powered up a splash screen appears indicating the serial number and firmware revision number.
After a brief moment the System Screen is displayed. Please refer to the Appendix for a logic diagram of all
the screen displays.
There is a 15-minute warm-up period after power is first applied. Under “AGMS”, "WARM UP" is displayed.
The green indicator on the AGM will blink during the warm-up period.
IMPORTANT: DO NOT plug the gas-sample hose or inlet port of any zone. The monitor will perform a vacuum
test during start up and a plugged zone will give a false indication.
System Screen