Bacharach AGM300 Smoke Alarm User Manual


 
36 Instruction 3015-4275
Navigating to the 2
nd
ADM Setup Screen
From ADM Setup Screen #1 press the MORE key to go to ADM Setup Screen #2. Press the BACK key to
return to ADM Setup Screen #1.
ADM Setup Screen #2
Setting Relay Parameters
This setting determines the function of relays 1 and 2 mounted inside the ADM unit.
1. Press the key adjacent to the relay parameter you want to adjust.
2. Use the UP/DOWN cursor keys to select unused, monitor on, evacuate, spill, leak, fault, or alarm.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
AGM Node Address
This value is the node address from 1 to 15 assigned to each AGM300 that is on the network. These values
must match the DIP switch settings on each AGM300 circuit board. Refer to the heading AGM Node Address
Dip Switch Settings on Page
11.
1. Press the key adjacent to the AGM# NODE you want to set.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.
Node Address DIP
Switches in AGM Unit