American Water Heater 318281-000 Water Heater User Manual


 
27
STARTUP / SYSTEM SETTINGS
The AC power cord should be plugged in to an appropriate 115V outlet. The controller will enter an initialization phase
in which the operating control lamp will flash red and green. After the initialization period the controller will be in
automatic operation with the default settings active.
The pre-adjusted system scheme is ARR 1. Other system settings are available, but this setting should not be
changed for the system included in this package.
The controller is now ready for operation. The following system settings should be made as indicated. The operational
system channels are listed in order of appearance by pressing the forward (1) button.
COL:
Collector Temperature
Display range: -40 to +482 °F
Shows the current collector temperature.
TST:
Tank temperature
Display range: -40 to +482 °F
Shows the current tank temperature (from tank bottom
sensor).
S3, S4:
Additional sensor temperature
Display range -40 to +482 °F
Shows the current temperature of the corresponding optional
sensor (without control function).
S3 and S4 are only indicated if the temperature sensors are
connected.
TRF:
Temperature return ow
Display range -40 to +482 °F
Shows the current temperature of the optional temperature
return ow sensor (S4) when the heat quantity measurement
option is activated.
hP:
Operating hours counter
Display channel
The operating hours counter adds up the solar operating
hours of the pump. Full hours are shown on the display.
The total operating hours can be reset. When the operating
hours channel is selected the symbol is permanently
shown in the display. The set button (3) must be pressed for
approximately 2 seconds in order to go into the reset mode
for the counter. The display symbol will be ashing and
the operating hours will be set to 0. In order to nish the reset
procedure the set button (3) must be pressed in order to
con rm.
In order to interrupt the reset procedure no button should be
pressed for about 5 seconds. The controller will automatically
return to the indication mode with the previous total.
Once the nal display channel is reached the remaining system setting channels may only be accessed by holding the forward
(2) button down for approximately 2 seconds. The following setting channels will then be shown:
ARR:
System arrangement setting
Shows the current system con guration setting. Arrangement
1 should be used for the system in this package and this
setting should not be changed.
DTO:
Switch-on temperature diff.
Adjustment range
2.0 to 40.0 °F
Default setting 12.0
Recommended setting: 10.0
Primarily the controller works in the same way as a standard
differential controller. If the switch-on difference, DT O
(collector temperature sensor reading minus the tank sensor
reading), is reached the pump is activated.