035-09651-001-A-0304
4 Unitary Products Group
FIG. 1 - UNIT SUSPENSION MOUNTING
(Horizontal Application)
Model
Power
Supply
Voltage Variation
1
Supply Air CFM
Entering Air Temperatures, °F
Cooling - wb Heating - db
Min. Max. Min. Max. Min. Max. Min. Max.
F3EH090
208/230-3-60 187 252
2400 3600 57 72 50
2
80460-3-60 414 506
380/415-3-50 342 456
F4EH120
208/230-3-60 187 252
3200 4800 57 72 50
2
80460-3-60 414 506
380/415-3-50 342 456
1
Utilization Range “A” in accordance with ARI Standard 110.
2
The system may operate below 50°F for a short period of time when warming up the conditioned space after a long shutdown.
TABLE 2 - APPLICATION DATA
Model Accessory
Based on a Standard Blower Motor
Center of Gravity
Dimensions, In.
Weight
Distribution, Lbs.
A B W1 W2 W3 W4 Total
F3EH090
Basic Unit Only 25-5/8 23-1/4 99 104 79 83 365
Unit with Electric Heat 30-3/4 23-3/8 90 150 72 121 433
Unit with Plenum 35-1/8 23-1/2 71 186 58 152 467
Unit with Electric Heat & Plenum 38 23-5/8 62 232 51 190 535
F4EH120
Basic Unit Only 24-1/8 23-1/4 116 106 93 85 400
Unit with Electric Heat 29-1/4 23-3/8 103 155 84 126 468
Unit with Plenum 33-3/8 23-1/2 88 190 70 154 502
Unit with Electric Heat & Plenum 36-5/8 23-5/8 76 236 63 195 570