MODEL
DCG
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.20 0.30 0.40 0.50 0.60 0.70 0.80
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
072
3200 1150 2325 1182 2425 1212 2525 - - - - - - - -
3000 1100 2010 1129 2090 1157 2150 1185 2225 1215 2290 1242 2360 - -
2800 1045 1700 1074 1780 1102 1850 1131 1940 1160 2025 1190 2075 1217 2130
2600 985 1425 1015 1475 1045 1540 1075 1630 1103 1715 1135 1760 1163 1825
2400 930 1240 958 1300 990 1350 1020 1400 1051 1430 1081 1490 1111 1600
2200 - - 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325
2000 - - - - - - 919 1025 950 1100 982 1130 1014 1160
1800 - - - - - - - - 909 925 939 1005 968 1030
DCG072 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)
MODEL
DCG
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
072
3200 - - - - - - - - - - - - - -
3000 - - - - - - - - - - - - - -
2800 1245 2190 - - - - - - - - - - - -
2600 1193 1920 1222 1990 1250 2060 - - - - - - - -
2400 1142 1675 1173 1730 1205 1800 1234 1885 - - - - - -
2200 1090 1380 1124 1450 1155 1550 1186 1640 1217 1710 1249 1775 - -
2000 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 1205 1545 1235 1600
1800 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360
NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*
INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS, AND THE HEAT EXCHANGERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN
GAS / ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS.
SUPPLY AIR BLOWER PERFORMANCE
-
DCG060 & 072 with Belt-Drive
MODEL
DCG
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.20 0.30 0.40 0.50 0.60 0.70 0.80
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
060
2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720
2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640
2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535
2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440
2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340
2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225
1900 - - - - 894 885 940 940 980 980 1014 1020 1047 1095
1800 - - - - 855 815 903 860 950 905 988 940 1022 970
1700 - - - - - - 884 815 925 850 964 880 1001 910
1600 - - - - - - 864 770 908 805 948 835 987 870
1500 - - - - - - - - 882 740 926 780 965 830
DCG060 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)
MODEL
DCG
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
060
2500 - - - - - - - - - - - - - -
2400 1193 1665 - - - - - - - - - - - -
2300 1170 1580 1202 1620 - - - - - - - - - -
2200 1148 1480 1180 1530 - - - - - - - - - -
2100 1121 1385 1155 1425 1190 1475 - - - - - - - -
2000 1100 1285 1133 1340 1169 1385 1205 1445 - - - - - -
1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 - - - -
1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 - - - -
1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - -
1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150
1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110
NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*
INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS, AND THE HEAT EXCHANGERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN
GAS / ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS.
530.18-TG1Y
Unitary Products Group 9