York 2000 Air Conditioner User Manual


 
ELECTRICAL DATA
-
Cooling / Electric Heating (DCE060 & 072) with Direct-Drive
MODEL
DCE
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
BREAKER
AMPS
KW STAGES
TOTAL
AMPS
060
208-1-60
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04503006
6.6
4.0
5.6
8.0
11.9
15.9
22.2
1
1
1
2
2
2
19.1
27.1
38.3
57.4
76.6
106.9
44.0
44.0
56.1
80.0
103.9
141.9
70
70
70
90
110
150
70
70
70
90
110
150
230-1-60
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
2CE04503006
6.6
5.3
7.5
10.6
15.9
21.2
29.6
1
1
1
2
2
2
22.1
31.3
44.2
66.3
88.3
123.3
44.0
47.3
63.5
91.1
118.7
162.4
70
70
70
100
125
175
70
70
70
100
125
175
208-3-60
2CE04500525*
2CE04500725*
2CE04501025
2CE04501525
2CE04502025
2CE04503025
6.6
4.0
5.6
8.0
11.9
15.9
22.2
1
1
1
2
2
2
11.0
15.6
22.1
33.1
44.2
61.7
27.9
27.9
35.9
49.7
63.5
85.4
40
40
40
50
70
90
40
40
40
50
70
90
230-3-60
2CE04500525*
2CE04500725*
2CE04501025
2CE04501525
2CE04502025
2CE04503025
6.6
5.3
7.5
10.6
15.9
21.2
29.6
1
1
1
2
2
2
12.7
18.0
25.5
38.2
51.0
71.2
27.9
30.8
40.1
56.1
72.0
97.3
40
40
45
60
80
100
40
40
45
60
80
100
460-3-60
2CE04500746*
2CE04501046*
2CE04501546*
2CE04502046*
2CE04503046*
3.3
6.8
10.1
13.6
19.5
28.8
1
1
1
2
2
8.2
12.1
16.4
23.5
34.6
14.3
19.3
24.6
33.4
47.4
20
20
25
35
50
20
20
25
35
50
575-3-60
2CE04501058
2CE04501558
2CE04502058
2CE04503058
3.3
10.6
15.9
21.2
30.4
1
1
2
2
10.2
15.3
20.4
29.3
16.9
23.2
29.6
40.7
20
25
30
45
072
208-3-60
2CE04500525*
2CE04500725*
2CE04501025
2CE04501525
2CE04502025
2CE04503025
6.8
4.0
5.6
8.0
11.9
15.9
22.2
1
1
1
2
2
2
11.0
15.6
22.1
33.1
44.2
61.7
33.5
33.5
36.1
49.9
63.7
85.6
50
50
50
50
70
90
50
50
50
50
70
90
230-3-60
2CE04500525*
2CE04500725*
2CE04501025
2CE04501525
2CE04502025
2CE04503025
6.8
5.3
7.5
10.6
15.9
21.2
29.6
1
1
1
2
2
2
12.7
18.0
25.5
38.2
51.0
71.2
33.5
33.5
40.4
56.3
72.2
97.5
50
50
50
60
80
100
50
50
50
60
80
100
460-3-60
2CE04500746*
2CE04501046*
2CE04501546*
2CE04502046*
2CE04503046*
3.6
6.8
10.1
13.6
19.5
28.8
1
1
1
2
2
8.2
12.1
16.4
23.5
34.6
17.2
19.7
24.9
33.8
47.8
25
25
25
35
50
25
25
25
35
50
575-3-60
2CE04501058
2CE04501558
2CE04502058
2CE04503058
3.6
10.6
15.9
21.2
30.4
1
1
2
2
10.2
15.3
20.4
29.3
17.2
23.6
30.0
41.1
20
25
30
45
1
Dual element, time delay type
2
Standard circuit breakers may be used in Canada and on applications
over 60 amps where the heaters are separately fused.
* These electric heaters DO NOT include a fuse box. If a fuse box is
required to meet a local code ((eg., Chicago), the following fuse
block accessories are available for field installation.
Electric Heat
Correction
Factors
Nominal Voltage Voltage
KW Cap
Multipier
208 208 1.00
240 230 0.92
480 460 0.92
600 575 0.92
Fuse Block
2FB04700425 208/240 Volts
2FB04700546 460 Volts
530.18-TG1Y
Unitary Products Group 13