York 2000 Air Conditioner User Manual


 
Front
DCE Units 24"
DCG Units 32"
Back
12" (Less Economizer)
36" (With Economizer
or Fixed Air/Motorized
Damper)
Left Side
(Filter Access)
24"(Less Economizer)
36" (With Economizer)
Right Side
(Cond. Coil)
24"
Below Unit
1
20"
Above Unit
2
72" (For Condenser
Air Discharge)
1 Units may be installed on combustible floors made from
wood or class A, B or C roof covering material.
2
Units must be installed oudoors. Overhanging structures
or shrubs should not obstruct condenser air discharge outlet.
NOTES:
DCE Models: Units and ductwork are approved for zero clearance to
combustible materials when equipped with electric heaters.
DCG Models: A 1" clearance must be provided between any combusti-
ble material and the supply air ductwork for a
distance of 3 feet from the unit.
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:
Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).
Four (4) feet below, 4 horizontal feet from, or 1 foot above
any door or gravity air inlet into the building.
Four (4) feet from electric meters, gas meters, regualtors
and relief equipment.
HOLE
KNOCKOUT
SIZE
(DIA.)
USED FOR
A7/8" *
Control Wiring
(Side or Bottom)**
B2" *
Power Wiring
(Side or Bottom)
C 1-5/8" Gas Piping (Front)
D 1-1/2" Gas Piping (Bottom)
*
Knockouts in the bottom of the unit can be located by the
slice in the insulation.
**
Do not remove the 2" knockout ring.
UTILITIES ENTRY DATA
UNIT DIMENSIONS
(DCE AND DCG - 3, 4, 5 & 6 TON)
RETURN AIR
SUPPLY AIR
CONDENSER AIR
OUTDOOR AIR
(Economizer)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
(Direct-Drive units)
SCROLL
COMPRESSOR
ACCESS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
(Direct-Drive units)
GAS SUPPLY ENTRY
(
1
2
“ NPTI AT GAS VALVE)
GAS SUPPLY ENTRY
(
1
2
“ NPTI AT GAS VALVE)
SCROLL COMPR.
ACCESS
CLEARANCES
All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.
530.18-TG1Y
Unitary Products Group 17