York 2000 Air Conditioner User Manual


 
SUPPLY AIR BLOWER PERFORMANCE
-
DCG036 & 048 with Belt-Drive
MODEL
DCG
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.20 0.30 0.40 0.50 0.60 0.70 0.80
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
036
1700 835 705 880 745 923 795 969 860 1013 970 - - - -
1600 811 655 854 695 898 740 942 790 986 840 1029 900 - -
1500 782 610 827 650 871 685 917 730 960 775 1003 825 1046 905
1400 - - 798 595 844 640 889 680 932 720 975 765 1018 790
1300 - - - - 816 590 862 635 907 675 951 715 995 750
1200 - - - - - - 834 585 881 630 927 665 970 705
1100 - - - - - - 809 550 855 590 900 625 942 665
1000 - - - - - - 782 510 829 545 872 858 919 625
900 - - - - - - - - 797 500 843 540 890 580
DCG036 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)
MODEL
DCG
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
036
1700 - - - - - - - - - - - - - -
1600 - - - - - - - - - - - - - -
1500 - - - - - - - - - - - - - -
1400 1055 875 - - - - - - - - - - - -
1300 1036 780 1066 850 - - - - - - - - - -
1200 1011 735 1047 765 1075 800 - - - - - - - -
1100 987 690 1028 720 1060 750 1084 775 - - - - - -
1000 963 655 1005 680 1040 695 1068 715 1089 735 - - - -
900 936 615 980 645 1020 660 1050 670 1053 680 1090 690 - -
NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*
INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS, AND THE HEAT EXCHANGERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN
GAS / ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS.
MODEL
DCG
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.20 0.30 0.40 0.50 0.60 0.70 0.80
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
048
2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235
1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170
1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100
1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030
1600 - - - - 818 665 858 740 898 820 940 890 980 950
1500 - - - - - - 842 695 882 755 922 835 962 895
1400 - - - - - - 833 650 867 705 904 765 942 820
1300 - - - - - - - - 858 665 893 725 932 785
1200 - - - - - - - - 847 640 880 680 916 730
DCG048 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)
MODEL
DCG
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
048
2000 1103 1270 - - - - - - - - - - - -
1900 1085 1210 - - - - - - - - - - - -
1800 1064 1145 1102 1180 - - - - - - - - - -
1700 1040 1075 1081 1115 1121 1140 - - - - - - - -
1600 1020 1005 1060 1050 1100 1085 - - - - - - - -
1500 1003 945 1044 995 1086 1035 - - - - - - - -
1400 982 880 1024 920 1067 965 1107 1000 - - - - - -
1300 970 835 1010 870 1053 920 1099 960 - - - - - -
1200 953 780 992 815 1034 855 1080 905 - - - - - -
NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*
INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS, AND THE HEAT EXCHANGERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN
GAS / ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS.
530.18-TG1Y
8 Unitary Products Group