York 2000 Air Conditioner User Manual


 
COOLING CAPACITIES
-
6 TON (DCE / DCG072)
Air On
Evaporator
Coil
Temperature of Air on Condenser Coil
105
°
F 115
°
F
To tal
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
To tal
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F Entering Dry Bulb,
°
F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2700
72 76 7.1 61 53 45 38 30 - - 75 7.9 59 51 43 36 28 - -
67 71 7.1 70 66 58 50 43 35 27 65 7.8 65 64 56 48 41 33 25
62 64 7.0 64 64 64 56 49 41 34 57 7.8 57 57 57 50 42 34 27
57 64 7.0 64 64 64 56 49 41 34 57 7.7 57 57 57 50 42 34 27
2550
72 76 7.1 59 51 44 37 29 - - 76 7.9 57 49 42 35 27 - -
67 71 7.1 69 64 56 49 42 34 27 66 7.9 66 61 54 47 40 32 25
62 64 7.0 64 64 64 56 49 42 35 58 7.8 58 58 58 51 43 36 29
57 64 7.0 64 64 64 56 49 42 34 58 7.7 58 58 58 50 43 36 29
2400
72 75 7.1 56 49 43 36 29 - - 76 8.0 55 48 41 34 27 - -
67 70 7.1 68 61 54 48 41 34 27 66 7.9 66 59 52 45 38 32 25
62 64 7.0 64 64 63 56 49 42 35 59 7.8 59 59 59 52 45 38 31
57 64 7.0 64 64 63 56 49 42 35 59 7.7 59 59 58 51 44 37 30
2100
72 73 7.1 52 45 39 33 27 - - 73 7.9 50 44 37 31 25 - -
67 68 7.1 63 56 50 44 38 32 26 63 7.8 61 54 48 42 36 30 24
62 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 54 48 42 35 29
57 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 53 47 41 35 29
1800
72 70 7.1 47 41 36 31 25 - - 69 7.8 45 40 34 29 23 - -
67 65 7.0 57 51 46 41 35 30 25 60 7.8 55 49 44 39 33 28 23
62 59 7.0 59 58 54 48 43 38 32 53 7.7 53 53 49 44 39 33 28
57 59 6.9 59 58 53 48 43 37 32 53 7.6 53 53 49 44 38 33 27
1
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the
motor heat, and deduct this heat from the gross capacity of the unit.
2
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36 KW. Refer to the Blower Performance
Table for the KW of the supply air blower motor.
ALL SENSIBLE CAPACITY
Air On
Evaporator
Coil
Temperature of Air on Condenser Coil
85
°
F95
°
F
To tal
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
To tal
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F Entering Dry Bulb,
°
F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2700
72 80 5.7 63 55 47 40 32 - - 77 6.3 63 55 47 40 32 - -
67 80 5.7 76 68 60 53 45 37 30 77 6.3 75 68 60 53 45 37 30
62 70 5.5 70 70 70 62 55 47 39 71 6.3 71 71 71 63 56 48 40
57 68 5.6 68 68 68 60 52 45 37 71 6.3 71 71 71 63 56 48 40
2550
72 82 5.7 60 53 46 38 31 - - 76 6.3 60 53 46 39 31 - -
67 82 5.7 73 65 58 51 43 36 29 76 6.3 73 66 58 51 44 36 29
62 71 5.5 71 71 70 62 55 48 41 70 6.3 70 70 69 62 55 48 40
57 69 5.6 69 69 69 62 55 47 40 70 6.3 70 70 70 62 55 48 40
2400
72 83 5.7 58 51 44 37 30 - - 75 6.3 58 51 44 37 30 - -
67 83 5.7 70 63 56 49 42 35 28 75 6.3 70 64 57 50 43 36 29
62 73 5.5 73 73 70 63 56 49 42 69 6.3 69 69 68 61 54 47 40
57 71 5.6 71 71 71 64 57 50 43 69 6.3 69 69 68 61 54 47 40
2100
72 79 5.7 54 48 41 35 29 - - 73 6.3 53 47 41 35 29 - -
67 79 5.7 65 59 53 47 40 34 28 73 6.3 65 59 52 46 40 34 28
62 69 5.5 69 69 66 60 54 47 41 67 6.3 67 66 63 57 51 45 38
57 67 5.6 67 67 67 61 54 48 42 67 6.3 67 66 63 57 51 45 39
1800
72 74 5.6 50 44 39 34 28 - - 71 6.3 49 43 38 33 27 - -
67 74 5.6 60 55 50 44 39 34 28 71 6.3 59 54 48 43 38 32 27
62 65 5.4 65 65 62 57 51 46 41 65 6.2 65 63 58 53 47 42 37
57 63 5.5 63 63 63 58 52 47 42 65 6.3 65 63 58 53 47 42 37
NOMINAL RATING
530.18-TG1Y
Unitary Products Group 7