York 2000 Air Conditioner User Manual


 
MODEL
ARI RATINGS
1
GAS HEAT CAPACITY
STANDARD
CFM
COOLING CAPACITY
80 / 67-95
°
F
SOUND
RATING
2
(dbels)
INPUT
(MBH)
OUTPUT
(MBH)
AFUE
(%)
S.S.E.
(%)
TEMP.
RISE
(
°
F)
GAS
LINE SIZE
(in. OD)
MBH SEER EER
DCG036N040
DCG036N079
36.0
36.0
10.00
10.00
9.10
9.10
82
82
50
100
40
79
80.9
80.5
81.6
80.8
15-45
40-70
1
2
1
2
1.300
DCG048N060
DCG048N099
47.4
47.4
10.00
10.00
9.00
9.00
82
82
75
125
59
99
80.9
80.3
81.6
80.6
25-55
45-75
1
2
1
2
1.700
DCG060N079
DCG060N099
59.0
59.0
10.00
10.00
9.10
9.10
82
82
100
125
79
99
80.5
80.3
80.8
80.6
25-55
35-65
1
2
1
2
2.100
DCG072N079
DCG072N099
72.0
4
72.0
4
-
-
9.00
9.00
84
84
100
125
79
99
80.5
80.3
80.8
80.6
25-55
35-65
1
2
1
2
2.400
1
Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
2
Rated in accordance with ARI Standard 270.
3
Heaters are available as accessories - all with single
point power supply.
4
Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360.
SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
EER = Energy Efficiency Ratio - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).
AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.
S.S.E. = Steady State Efficiency. (Percent Output).
RATINGS
MODEL
ARI RATINGS
1
NOMINAL
ELECTRIC HEAT CAPACITY
3
(KW)
STANDARD
CFM
COOLING CAPACITY
80 / 67-95
°
F
SOUND
RATING
2
(dbels)
MBH SEER EER 240V 480V 600V
DCE036 36.0 10.00 9.10 82
5, 7, 10,
15 & 20
7, 10,
15 & 20
10,
15 & 20
1.300
DCE048 47.4 10.00 9.00 82
5, 7, 10,
15 & 20
7, 10,
15 & 20
10,
15 & 20
1.700
DCE060 59.0 10.00 9.10 82
5, 7, 10,
15, 20 & 30
7, 10, 15
20 & 30
10, 15,
20 & 30
2.100
DCE072 72.0 - 9.00 84
5, 7, 10,
15, 20 & 30
7, 10, 15,
20 & 30
10, 15,
20 & 30
2.400
CAPACITY RATINGS - Cooling / Gas Heating
CAPACITY RATINGS - Cooling / Electric Heating
= Not ARI Listed.
PHYSICAL DATA -
BASIC UNITS
MODEL
EVAPORATOR
BLOWER
EVAPORATOR
COIL
COMPRESSOR
TYPE
CONDENSER
FAN
CONDENSER
COIL
AIR
FILTERS
(SEE NOTE)
CHARGE
CENTRIFUGAL
(Dia. x Wd. in.)
FAN MOTOR HP
(DIRECT-DRIVE)
FAN MOTOR HP
(BELT-DRIVE)
ROWS DEEP
FINS PER INCH
FACE AREA
(Sq. Ft.)
HERMETICALLY
SEALED
PROPELLER
DIA. (in.)
FAN MOTOR HP
NOM. CFM TOTAL
ROWS DEEP
FINS PER INCH
FACE AREA
(Sq. Ft.)
QUANTITY
PER UNIT
(15" X 20" X 1")
QUANTITY
PER UNIT
(14" X 25" X 1")
TOTAL FACE
AREA (sq. ft.)
REFRIGERANT
R-22 (lbs./oz.)
036 12 x 10
1
2
1
1
2
3133.6
SCROLL
TYPE
24
1
4
3,400 1 16 17.1 2 1 6.3 5/8
048 12 x 10
3
4
1
1
2
3134.3 24
1
4
3,400 1 16 17.1 2 1 6.3 6/8
060 12 x 10 1 1
1
2
3135.1 24
1
4
3,400 1 22 17.1 2 1 6.3 6/8
072 12 x 11 1 1
1
2
4135.1 24
1
4
3,300 2 16 16.7 2 1 6.3 10/0
NOTE: Filter racks are adapted for 1" or 2" thick filters.
SOUND POWER RATINGS FOR SUPPLY AIR BLOWER
MODEL CFM
ESP BLOWER
SOUND POWER (dB 10
-12
watts)
OCTAVE BAND CENTERLINE FREQUENCY (Hz)
SWL
dB (A)
dB (A)
@
10 ft.
*
IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000
0361,2000.60LOW0.6084847467696257527441
048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42
060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43
072 2,200 0.30 HIGH 1.35 87 87 77 70 72 65 60 55 77 44
* At a distance of 10 ft.from the blower.
NOTE: These values have been derived using a model of sound propagation, measuring the indoor ambient sound levels ten feet from the source. The dBA values provided are for reference
only. Calculation of dBA values cover matters of system design and application. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in
any other form than sound power level ratings.
530.18-TG1Y