York 2000 Air Conditioner User Manual


 
Air On
Evaporator
Coil
Temperature of Air on Condenser Coil
105
°
F 115
°
F
To tal
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
To tal
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F Entering Dry Bulb,
°
F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2500
72 61 6.1 48 41 35 29 22 - - 57 6.7 46 39 33 27 20 - -
67 55 5.9 55 52 46 39 33 27 20 50 6.6 50 50 43 37 31 24 18
62 49 5.9 49 49 49 42 36 30 23 44 6.5 44 44 44 38 31 25 19
57 47 5.9 47 47 47 40 34 28 21 42 6.5 42 42 42 36 30 23 17
2250
72 61 6.0 45 39 33 28 22 - - 57 6.6 43 38 32 26 20 - -
67 54 5.9 53 49 44 38 32 26 20 50 6.5 50 47 42 36 30 24 18
62 48 5.8 48 48 48 42 37 31 25 44 6.4 44 44 44 38 32 26 20
57 46 5.8 46 46 46 40 35 29 23 42 6.4 42 42 42 36 31 25 19
2000
72 60 6.0 42 37 32 26 21 - - 57 6.6 41 36 30 25 20 - -
67 54 5.8 52 47 41 36 31 25 20 50 6.5 50 45 40 34 29 24 18
62 48 5.7 48 48 48 43 37 32 27 44 6.4 44 44 44 38 33 28 22
57 46 5.8 46 46 46 41 35 30 25 42 6.3 42 42 42 37 32 26 21
1750
72 57 6.0 38 34 29 24 19 - - 53 6.5 37 32 27 23 18 - -
67 51 5.8 47 42 38 33 28 24 19 46 6.4 45 41 36 31 26 22 17
62 45 5.7 45 45 44 39 34 30 25 41 6.3 41 41 39 35 30 25 21
57 43 5.8 43 43 42 37 32 28 23 39 6.3 39 39 38 33 29 24 19
1500
72 54 6.0 34 30 26 22 18 - - 49 6.5 33 28 24 20 16 - -
67 48 5.8 42 38 34 30 26 22 18 43 6.4 40 36 32 28 24 20 16
62 43 5.7 43 43 39 35 31 27 23 38 6.3 38 38 35 31 27 23 19
57 41 5.8 41 41 38 34 30 26 21 37 6.2 37 37 34 30 26 22 18
1
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the
motor heat, and deduct this heat from the gross capacity of the unit.
2
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36 KW. Refer to the Blower Performance
Table for the KW of the supply air blower motor.
ALL SENSIBLE CAPACITY
Air On
Evaporator
Coil
Temperature of Air on Condenser Coil
85
°
F95
°
F
To tal
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
To tal
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F Entering Dry Bulb,
°
F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2500
72 68 4.9 50 44 38 32 25 - - 65 5.6 50 43 37 31 24 - -
67 62 4.8 62 56 50 43 37 31 24 60 5.3 60 54 48 42 35 29 23
62 57 4.7 57 57 57 51 44 38 32 53 5.3 53 53 53 47 41 34 28
57 55 4.7 55 55 55 48 42 36 29 51 5.4 51 51 51 44 38 32 25
2250
72 67 4.9 48 42 36 30 24 - - 65 5.4 47 41 35 29 23 - -
67 62 4.8 59 53 47 41 35 30 24 59 5.2 57 51 45 40 34 28 22
62 56 4.7 56 56 56 50 45 39 33 53 5.2 53 53 53 47 41 35 29
57 54 4.7 54 54 54 48 42 36 31 50 5.3 50 50 50 44 39 33 27
2000
72 66 4.9 45 39 34 29 23 - - 64 5.3 44 39 33 28 22 - -
67 61 4.8 55 50 44 39 34 28 23 58 5.1 54 48 43 38 32 27 22
62 55 4.7 55 55 55 50 45 39 34 52 5.1 52 52 52 47 42 36 31
57 53 4.6 53 53 53 48 42 37 32 50 5.2 50 50 50 44 39 34 28
1750
72 63 4.8 41 36 31 27 22 - - 61 5.4 40 35 31 26 21 - -
67 58 4.7 51 46 41 36 32 27 22 56 5.1 49 44 39 35 30 25 21
62 53 4.6 53 53 51 47 42 37 32 50 5.2 50 50 48 43 39 34 29
57 51 4.6 51 51 49 44 40 35 30 47 5.2 47 47 46 41 36 32 27
1500
72 60 4.8 37 33 29 25 21 - - 58 5.4 36 32 28 24 20 - -
67 56 4.7 46 42 38 34 30 26 21 53 5.2 44 40 36 32 28 24 20
62 51 4.6 51 51 47 43 39 35 31 47 5.2 47 47 44 40 36 32 27
57 49 4.6 49 49 45 41 37 33 29 45 5.3 45 45 42 38 34 29 25
NOMINAL RATING
COOLING CAPACITIES
- 5 TON (DCE / DCG060)
530.18-TG1Y
6 Unitary Products Group