Yeoman PR1145 Stove User Manual


 
C
A
B
A = 643mm
B = 43mm
C = 12mm
AR0604
1
4.2 This appliance must not be installed in a room that contains
a bath or shower.
4.3 The stove is not suitable for installation against a
combustible wall; all combustible materials must be
removed from the area behind the stove.
4.4 Ensure that all minimum clearances to combustible
materials are complied with (see Diagrams 2 & 3).
AR0522
150
225
150
2
3
50mm
150mm
AR0531
The above dimensions provide adequate clearance to
combustible materials. It may be necessary to add
additional clearance so that the controls can be reached
and spillage tests performed when necessary.
10
INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
1. FLUE AND CHIMNEY REQUIREMENTS
1.1 The chimney or flue system must comply with the rules in
force, and must be a minimum of 127mm (5") in diameter.
1.2 The minimum effective height of the flue or chimney must
be 3 metres (10ft). Any horizontal flue run from the rear
outlet should not exceed 100mm from the back of the
appliance.
1.3 The chimney or flue must be free from any obstruction. Any
damper plates should be removed or secured in the fully
open position, and no restrictor plates should be fitted.
1.4 The chimney should be swept prior to the installation of the
appliance. However, where it can be seen that the chimney
is clean and unobstructed throughout its entire length, it
need not be swept.
1.5 If the stove is to be fitted into an existing brick built
chimney without a closure plate, a 127mm (5") liner must
be used. Larger lined flues may work, but in some instances
could cause cold start flue problems resulting in nuisance
shutdown. Lined flues above 175mm (7") are not
recommended.
1.6 Due to recent changes to European chimney standards, new
flues and chimneys are now classified by their resistance to
temperature, pressure, corrosion, condensation and fire. To
assist in identifying the correct flue system, the minimum
flue specification is shown in Installation Instructions,
Technical Specification (page 8). Existing chimneys are not
covered by this system.
2. VENTILATION
2.1 Consult the rules in force.
Note: This appliance does not normally require any
additional ventilation when installed in G.B.
3. INSTALLATION OF THE GAS SUPPLY
9.1 Before installation ensure the stove is compatible with the
local gas type and pressure.
9.2 Ensure the gas supply delivers the required amount of gas in
accordance with the rules in force.
9.3 Soft copper tubing and soft soldered joints must be no
closer than 50mm to the base of the burner unit.
9.4 Ensure a means of isolating the gas supply, independent of
the stove's controls is provided.
9.5 All gas supply pipes must be purged of any debris before
connection to the stove.
4. LOCATION
4.1 This appliance must stand on a non-combustible hearth that
is at least 12mm thick, and projects a minimum of 50mm
from the base of the stove in all directions (see Diagram 1).